Ductwork Fabrication

HVAC Fundamentals

100 min read Training Guide

An overview of heating, ventilation, and air conditioning systems, covering the refrigeration cycle, major components, and common troubleshooting approaches.

Table of contents

HVAC Fundamentals

Heating, ventilation, and air conditioning (HVAC) systems maintain comfort and air quality in every type of building - from single-family homes to hospitals, factories, and high-rise offices. As an HVAC apprentice, you need to understand the physics of heat transfer, the refrigeration cycle, how each major component works, system types, refrigerant handling requirements, and a systematic approach to diagnosis and repair. This guide provides the foundational knowledge you will build on throughout your career.

The Physics of Comfort

HVAC is fundamentally about moving heat from where it is not wanted to where it is wanted (or to where it can be rejected). Three key concepts:

Heat Transfer Methods

  • Conduction - Heat flows through solid materials by direct contact. Example: a metal pot handle gets hot on the stove. In HVAC: heat conducts through building walls, windows, and ductwork.
  • Convection - Heat transfers through moving fluid (air or liquid). Example: warm air rising from a heating register. In HVAC: forced convection (fan-driven airflow over a coil) is the primary heat transfer method.
  • Radiation - Heat transfers through electromagnetic waves without needing a medium. Example: warmth from the sun through a window. In HVAC: radiant floor heating and solar heat gain through windows.

Temperature and Heat

  • Temperature is measured in degrees Fahrenheit (F) or Celsius (C). It describes the intensity of heat.
  • Heat is measured in BTUs (British Thermal Units). One BTU is the amount of heat needed to raise 1 pound of water by 1 degree F.
  • A system's capacity is rated in BTUs per hour (BTU/h) or tons. 1 ton of cooling = 12,000 BTU/h. A typical residential system is 2 to 5 tons.

Sensible vs. Latent Heat

  • Sensible heat causes a temperature change that you can measure with a thermometer. Heating air from 70 degrees F to 95 degrees F is adding sensible heat.
  • Latent heat causes a phase change without changing temperature. Boiling water (212 degrees F liquid to 212 degrees F steam) absorbs latent heat. In HVAC, removing moisture from air (dehumidification) involves removing latent heat.
  • Total cooling load = sensible load + latent load. Both must be addressed for comfort.

The Refrigeration Cycle

The refrigeration cycle is the core principle behind all air conditioning, heat pump, and refrigeration systems. It moves heat from a low-temperature area (where you want cooling) to a high-temperature area (where you reject the heat) using a refrigerant that changes between liquid and gas states.

The Four Components and Their Functions

1. Compressor - The heart of the system.

  • Receives low-pressure, low-temperature refrigerant gas from the evaporator
  • Compresses it into high-pressure, high-temperature gas
  • The compression raises both pressure and temperature, enabling the refrigerant to reject heat to the outdoor air (which is at a lower temperature than the compressed gas)
  • Types: Reciprocating (piston), scroll (most common in residential), rotary, screw (commercial), centrifugal (large commercial/industrial)
  • Lubricated by oil that circulates with the refrigerant. Oil return to the compressor is critical - refrigerant piping must be sized and sloped to ensure oil travels through the system and returns

2. Condenser - The heat rejection component.

  • High-pressure, high-temperature gas from the compressor enters the condenser coil
  • Outdoor air (or water in water-cooled systems) passes over the coil
  • The refrigerant releases its heat to the outdoor air (or water) and condenses from a gas to a high-pressure liquid
  • Subcooling: The liquid refrigerant is cooled a few degrees below its condensing temperature. Normal subcooling: 10-15 degrees F. Subcooling confirms the condenser is fully flooded with liquid.
  • The condenser fan pulls outdoor air across the coil. A dirty coil or restricted airflow causes high head pressure and reduced efficiency.

3. Metering Device (Expansion Device) - The flow control.

  • Receives high-pressure liquid from the condenser
  • Drops the pressure and temperature dramatically by restricting flow through a small orifice
  • Types:
    • TXV (Thermostatic Expansion Valve) - Maintains a constant superheat at the evaporator outlet by modulating flow based on a sensing bulb attached to the suction line. Most common in residential systems.
    • Fixed orifice (piston) - A simple, fixed restriction. Less precise than a TXV but has no moving parts. Still found in some residential systems.
    • EEV (Electronic Expansion Valve) - Electronically controlled for precise refrigerant metering. Used in higher-efficiency systems and VRF (variable refrigerant flow) systems.

4. Evaporator - The heat absorption component.

  • Low-pressure, low-temperature liquid/gas mixture from the metering device enters the evaporator coil
  • Indoor air passes over the coil (blown by the indoor blower motor)
  • The refrigerant absorbs heat from the indoor air and evaporates from liquid to gas
  • Superheat: The gas is heated a few degrees above its boiling point before reaching the compressor. Normal superheat: 8-14 degrees F. Superheat confirms all liquid has evaporated before entering the compressor (liquid entering the compressor causes catastrophic damage - called "liquid slugging" or "floodback").
  • As warm, humid air passes over the cold evaporator coil, moisture condenses on the coil surface (dehumidification). This condensate drains to a pan and through a condensate drain line.

Superheat and Subcooling - Why They Matter

These are the two most important diagnostic measurements in refrigeration:

Superheat (measured at the evaporator outlet/suction line):

  • Superheat = Suction line temperature - Saturated suction temperature (from pressure/temperature chart)
  • Low superheat (below 5 degrees F) means liquid refrigerant may reach the compressor - risk of compressor damage
  • High superheat (above 20 degrees F) means the evaporator is starved for refrigerant - reduced capacity and efficiency
  • Causes of abnormal superheat: incorrect charge, restricted metering device, dirty evaporator, low airflow, TXV malfunction

Subcooling (measured at the condenser outlet/liquid line):

  • Subcooling = Saturated condensing temperature - Liquid line temperature
  • Low subcooling (below 5 degrees F) may indicate undercharge or restricted condenser
  • High subcooling (above 20 degrees F) may indicate overcharge or restricted metering device
  • Subcooling is the primary charging method for systems with a TXV

System Types

Split Systems (Most Common Residential)

  • Outdoor unit (condensing unit): compressor + condenser coil + condenser fan
  • Indoor unit: evaporator coil + blower, paired with a furnace or air handler
  • Connected by refrigerant lines (suction and liquid) and control wiring
  • Most residential AC and heat pump systems use this configuration

Package Units

  • All components (compressor, condenser, evaporator, blower) in a single outdoor cabinet
  • Common in commercial rooftop installations and some residential applications
  • Ductwork connects directly to the unit

Heat Pumps

  • An air conditioner that can reverse the refrigeration cycle to provide heating
  • A reversing valve (4-way valve) switches the direction of refrigerant flow
  • In cooling mode: indoor coil is the evaporator, outdoor coil is the condenser (same as standard AC)
  • In heating mode: outdoor coil becomes the evaporator (absorbing heat from outdoor air), indoor coil becomes the condenser (releasing heat indoors)
  • Heat pump efficiency decreases as outdoor temperature drops. Below the balance point (typically 30-40 degrees F), supplemental heat (electric heat strips or a gas furnace) is needed.
  • Defrost cycle: When the outdoor coil (acting as evaporator in heating mode) ices up, the system temporarily reverses to melt the ice. This is normal operation.

Mini-Split (Ductless) Systems

  • Wall-mounted indoor units connected to an outdoor condensing unit
  • No ductwork required - each indoor unit conditions a single zone
  • Multi-zone systems connect multiple indoor units to one outdoor unit
  • Inverter-driven compressors modulate capacity for precise temperature control and high efficiency
  • Installation requires refrigerant piping, condensate drain, power, and communication wiring between indoor and outdoor units

Refrigerants

Common Refrigerants

  • R-410A - The current standard for residential and light commercial AC and heat pumps. Operates at higher pressures than R-22 (approximately 120 PSI suction, 350-400 PSI discharge at typical conditions). Requires POE (polyolester) oil.
  • R-22 - The former standard, phased out due to ozone depletion. Production and import banned in the US since January 2020. Can only be used from reclaimed stocks.
  • R-32 - Newer refrigerant with lower global warming potential. Being adopted in some residential equipment.
  • R-134a - Common in automotive AC and medium-temperature commercial refrigeration.
  • R-404A / R-507A - Common in commercial refrigeration (supermarket cases, cold storage).

EPA Section 608 Certification

Federal law requires EPA Section 608 certification to purchase or handle refrigerants. Four certification types:

  • Type I - Small appliances (less than 5 lbs of refrigerant): window units, refrigerators, PTACs
  • Type II - High-pressure equipment: residential AC, heat pumps, commercial AC
  • Type III - Low-pressure equipment: centrifugal chillers
  • Universal - All types (recommended - take the full exam)

Key regulations:

  • It is illegal to knowingly vent refrigerant into the atmosphere (Section 608)
  • Recover refrigerant before opening a system or disposing of equipment
  • Use only EPA-approved recovery equipment
  • Keep records of refrigerant purchased, recovered, and recycled
  • Violation penalties can reach $44,539 per day per violation

Essential HVAC Tools

Temperature and Pressure:

  • Digital manifold gauge set (or analog manifold with digital thermometer) - measures suction and discharge pressures, calculates superheat and subcooling
  • Clamp-on thermometers for pipe temperature measurement
  • Infrared thermometer for surface temperatures
  • Psychrometer or hygrometer for wet-bulb and humidity measurements

Electrical:

  • Digital multimeter (voltage, current, resistance, capacitance)
  • Clamp-on ammeter for measuring motor current
  • Capacitor tester (many multimeters include this)
  • Megohmmeter for compressor winding insulation testing

Airflow:

  • Anemometer for measuring air velocity at registers
  • Manometer for measuring static pressure in the duct system
  • Balancing hood for measuring CFM at supply registers

Refrigerant Handling:

  • Recovery machine and recovery tank
  • Vacuum pump (minimum 5 CFM for residential, 8+ CFM for commercial)
  • Micron gauge (for verifying vacuum levels - must reach 500 microns or lower)
  • Refrigerant scale (accurate to 0.1 oz for precise charging)
  • Leak detector (electronic sniffer or UV dye method)
  • Nitrogen regulator and dry nitrogen (for pressure testing and brazing)

Systematic Troubleshooting

When a system is not working, follow this structured approach:

Step 1: Gather Information

  • What is the complaint? (No cooling? No heating? Weak airflow? Strange noise?)
  • When did it start? What changed?
  • Has any work been done recently?

Step 2: Check the Obvious

  • Thermostat set correctly? Batteries good?
  • Breakers on (both indoor and outdoor)?
  • Outdoor disconnect in the ON position?
  • Air filter clean?
  • Supply and return registers open and unobstructed?

Step 3: Measure and Diagnose

For cooling complaints:

  1. Check the air filter (dirty filter = restricted airflow = frozen coil)
  2. Measure supply and return air temperatures. Normal split: 15-22 degrees F across the evaporator coil.
  3. Check suction pressure and superheat
  4. Check discharge pressure and subcooling
  5. Check compressor amp draw against nameplate RLA (rated load amps)
  6. Check condenser coil for dirt and debris
  7. Check airflow across evaporator (static pressure measurement)

For heating complaints (gas furnace):

  1. Check thermostat call for heat
  2. Verify gas supply is on
  3. Check the ignition sequence: inducer motor starts, pressure switch closes, igniter heats, gas valve opens, flame sensor detects flame
  4. Check the flame sensor (most common furnace failure - a dirty sensor causes intermittent ignition failure). Clean with fine emery cloth.
  5. Check flue for blockage
  6. Check the heat exchanger for cracks (visual inspection and combustion analysis)

Step 4: Common Problems and Their Signatures

Symptom Likely Cause Key Measurement
No cooling, compressor not running Bad capacitor, contactor, or compressor Voltage at contactor, capacitor test, compressor ohms
Cooling but not cold enough Low charge, dirty coil, restricted airflow Superheat, subcooling, temperature split
Frozen evaporator coil Low airflow or low charge Filter condition, static pressure, superheat
Short cycling (frequent on/off) Dirty filter, bad thermostat, oversized system Filter, thermostat differential, system sizing
High electric bills Dirty coils, low charge, duct leaks Clean coils, check charge, test duct leakage
Compressor runs but no cooling No refrigerant (major leak), failed compressor valves Suction/discharge pressures (both near equalized = valve failure)

Preventive Maintenance Procedures

Regular maintenance prevents the majority of HVAC service calls and extends equipment life. Here is what a thorough maintenance visit includes:

Cooling Season Maintenance

Outdoor unit (condensing unit):

  1. Disconnect power and verify zero energy
  2. Remove debris (leaves, grass clippings, cottonwood seeds) from the coil
  3. Clean the condenser coil with a garden hose from the inside out (gentle spray, not high-pressure)
  4. Straighten bent fins with a fin comb
  5. Check the contactor contacts for pitting and arcing damage - replace if contacts are pitted through
  6. Test the run capacitor and start capacitor with a capacitor tester. Capacitors are the most common failure on residential systems. Replace any capacitor more than 10% from its rated microfarad value.
  7. Check the compressor amp draw with a clamp meter - compare to the RLA on the nameplate
  8. Inspect the wiring for loose connections, burned insulation, and heat damage
  9. Verify the condensate drain is clear by pouring water into the drain pan
  10. Check the refrigerant charge using superheat (fixed orifice systems) or subcooling (TXV systems) - do NOT add refrigerant unless measurements confirm a low charge

Indoor unit (air handler/furnace with evaporator):

  1. Replace or clean the air filter
  2. Check the evaporator coil for dirt buildup (accessible coils only - some require panel removal)
  3. Clean the condensate drain pan and drain line with a wet/dry vacuum and algaecide tablets
  4. Check the blower wheel for dirt buildup - a dirty blower wheel reduces airflow significantly
  5. Check the blower motor amp draw and compare to nameplate
  6. Verify the supply-return temperature split (should be 15-22 degrees F for cooling)

Heating Season Maintenance (Gas Furnace)

  1. Replace or clean the air filter
  2. Inspect the heat exchanger for cracks (visual inspection using a strong light and mirror). A cracked heat exchanger can leak carbon monoxide into the living space and requires immediate replacement.
  3. Clean the flame sensor with fine emery cloth or a dollar bill - a dirty flame sensor is the number one cause of "no heat" calls on gas furnaces
  4. Inspect the igniter for cracks (hot surface igniters are fragile ceramic - handle carefully)
  5. Check the inducer motor for proper operation and unusual noise
  6. Verify the pressure switch closes when the inducer runs
  7. Check gas pressure at the manifold (consult the rating plate for proper inlet and manifold pressure)
  8. Perform combustion analysis: measure CO and CO2 in the flue. Acceptable CO levels in the flue vary by manufacturer but generally should be under 100 PPM (air-free). Any CO in the living space above 9 PPM warrants investigation.
  9. Check the flue pipe for proper slope, secure connections, and no blockages
  10. Verify the thermocouple or flame rod microamp reading (flame rod: minimum 1.0 microamp, ideally 2.0+ microamps)

Common Mistakes Apprentice HVAC Technicians Make

  1. Adding refrigerant without measuring superheat or subcooling - "It seems low" is not a diagnosis. Overcharging is just as damaging as undercharging. Always measure before adjusting charge.

  2. Not checking the air filter first - The filter affects everything. A dirty filter can cause frozen coils, high head pressure, poor airflow, and short cycling. Always check it first.

  3. Forgetting to check the capacitor - Run capacitors fail gradually, causing hard starting, high amp draw, and eventual compressor failure. A simple capacitance test takes 30 seconds and prevents expensive callbacks.

  4. Not purging with nitrogen when brazing - Brazing copper tubing without a nitrogen purge creates copper oxide scale inside the system. These particles circulate with the refrigerant and can plug metering devices, damage compressor valves, and reduce system life.

  5. Overcharging the system - Adding refrigerant to a system with an airflow problem does not fix the airflow problem. It makes things worse by flooding liquid back to the compressor.

  6. Not evacuating properly before charging - The system must be pulled to 500 microns or less and held for at least 10 minutes. Moisture left in the system reacts with refrigerant to form acids that destroy the compressor.

  7. Ignoring electrical connections - Loose wire connections cause arcing, heat damage, and intermittent failures. Check and tighten every connection during maintenance.

  8. Not verifying airflow - Many technicians focus only on the refrigerant side. Without adequate airflow across the evaporator (typically 400 CFM per ton), even a perfectly charged system will not perform.

Tips from Experienced Technicians

  • Carry a mirror and a strong flashlight. You will inspect heat exchangers, evaporator coils, and connections in spaces you cannot see directly.
  • Keep a log of every system you service. Record pressures, temperatures, amp draws, and any observations. When a customer calls back in six months, your notes tell you exactly where you left off.
  • Learn to read the diagnostic LED codes on furnace circuit boards. Most modern furnaces have a blinking LED that tells you exactly what fault occurred. The code legend is usually printed inside the furnace access panel.
  • Temperature split (supply minus return) is your quickest sanity check. For cooling, 15-22 degrees F is normal. For heating, 40-70 degrees F (gas furnace) is normal. Anything outside these ranges tells you something is wrong.
  • When a compressor will not start but hums, check the capacitor first, then check for a locked rotor (measure ohms between start and common). A failed capacitor is a $15 part. A failed compressor is a $1,500+ repair.

Safety Protocols

  • Electrical safety - Always verify power is off before working on equipment. Capacitors in outdoor units store lethal charges - discharge before servicing. The dual run capacitor in a condensing unit can hold 370-440V AC even after the disconnect is pulled.
  • Refrigerant safety - Refrigerants are heavier than air and can displace oxygen in confined spaces. R-410A operates at very high pressures (up to 600+ PSI on the high side in extreme conditions) - never exceed the rated working pressure of your hoses and gauges. Always wear safety glasses when connecting or disconnecting gauge hoses.
  • Combustion safety - Gas furnaces produce carbon monoxide. Always test CO levels in the flue and living space. A cracked heat exchanger can introduce CO into the home's air supply. Carry a personal CO detector.
  • Rooftop safety - Commercial HVAC work is often on rooftops. Follow fall protection requirements per OSHA when working within 6 feet of an unprotected edge. Never work alone on a roof.
  • Brazing safety - Brazing refrigerant joints requires an oxy-acetylene or air-acetylene torch. Purge the system with dry nitrogen while brazing to prevent oxidation inside the tubing. Keep a fire extinguisher within reach. Verify no refrigerant remains in the section being brazed - refrigerant decomposes at high temperatures and produces phosgene gas, which is toxic.
  • Ladder safety - HVAC technicians use ladders constantly. Maintain three points of contact, set the angle at 4:1 (base 1 foot out for every 4 feet of height), and never overreach.

Key Takeaways

  • The refrigeration cycle has four components: compressor, condenser, metering device, evaporator
  • Superheat and subcooling are the two most important diagnostic measurements
  • EPA Section 608 certification is legally required to handle refrigerants
  • Always check the simple things first: thermostat, breakers, air filter, disconnect
  • Heat pumps reverse the refrigeration cycle for heating - the reversing valve is the key component
  • Regular maintenance (filter changes, coil cleaning, electrical checks) prevents most service calls
  • Never vent refrigerant to the atmosphere - recover, recycle, or reclaim