Skip to content
Insulation Installation

Insulation Installation

15 min read Training Guide

Seal air leaks, then install batts, blown-in and foam insulation with no gaps or compression, and place vapor retarders where the climate calls for them.

Table of contents

Insulation only works if it is installed correctly. A wall can have the right R-value printed on the bag and still leak heat through gaps, compressed batts and air leaks around wires. Bad work costs the owner money each month, and in the wrong spot it can trap moisture and rot a wall from the inside. Good installers fill every cavity completely, and they seal the air leaks first.

Energy codes change often and vary by state and town. Your plans and the locally adopted code set the required R-values and vapor rules. This guide teaches the methods that apply everywhere.

What You Will Be Able to Do

  • Explain R-value, heat flow and thermal bridges.
  • Air seal the common leak points before insulating.
  • Install batts with no gaps, voids or compression.
  • Describe how blown-in and spray foam insulation are installed and checked.
  • Place a vapor retarder correctly for the climate.

How Heat Moves

Heat always moves from warm to cold, in three ways:

  • Conduction. Through solid materials, like heat moving through a stud.
  • Convection. Carried by moving air, like a draft through a gap.
  • Radiation. Through space, like the sun heating a roof.

R-value measures resistance to heat flow. A higher number means better resistance. R-values add up, so two layers of R-13 equal R-26. The rating assumes correct installation, and a batt is mostly trapped air.

A thermal bridge is a structural part that conducts heat through the insulated layer. Studs, headers and steel framing are the usual ones. Continuous insulation over the outside of the framing reduces them.

Material R-value per inch
Fiberglass batt About R-3.2 (range 3.0 to 3.7)
Mineral wool batt R-3.0 to R-4.2
Cellulose, blown R-3.2 to R-3.8
Fiberglass, blown R-2.2 to R-2.7
Open-cell spray foam R-3.5 to R-3.7
Closed-cell spray foam R-6.0 to R-7.0
Rigid XPS R-5
Rigid EPS R-3.8 to R-4.4
Rigid polyiso R-5.7 to R-6.5

How Much Is Required

Requirements depend on climate zone and code edition. R-38 was long the common benchmark for attics. Recent energy codes run from about R-30 in the hottest zones up to R-49 or R-60 elsewhere. Do not rely on memory or an old chart. Read the plan and the locally adopted code.

Air Seal First

Air sealing closes gaps and cracks to stop air leaks, which insulation alone does not do. Most insulation lets air pass through it. Air sealing must come first, because once insulation is in, it covers the leaks and they cannot be reached.

Leak point How to seal
Top and bottom plates Caulk, foam or gasket
Rim joists Rigid foam cut to fit, or spray foam
Wire and pipe holes Caulk or foam, firestop where rated
Recessed lights Replace with IC-rated airtight fixtures
Duct boots Mastic
Attic hatch Weatherstrip, insulate the hatch
Chimney chase Sheet metal and high-temperature sealant

Caulk fits gaps up to about 1/4 inch. Canned foam handles larger ones. Do not use foam against chimneys or flues, because it can burn. Use firestop products through fire-rated walls and floors.

Installing Batts

Batts come faced or unfaced, in widths for 16- and 24-inch framing. Mineral wool is denser, holds its shape better and resists fire and water better than fiberglass, and it costs more.

Fit Each Cavity

  1. Measure and cut. Cut each batt about 1 inch long for a friction fit, and to width for odd bays. Compress it against a board and slice with a sharp utility knife.
  2. Fill the bay. The batt should touch the studs, the top plate and the bottom plate, front and back. A bay with gaps performs far worse than the gap area suggests, because air moves around inside.
  3. Do not compress. Compressing a batt squeezes out the air pockets that give it resistance. An R-19 batt that is 6-1/4 inches thick, stuffed into a 3-1/2-inch wall, drops to roughly R-12 or R-13. It is wasted money.
  4. Split around wires and pipes. Peel the batt into two thinner layers. Slide one layer behind the wire and the other in front. Do not push the whole batt behind it.
  5. Cut around boxes. Cut the batt to fit snugly around electrical boxes. Stuffing it behind the box leaves an air gap, so heat bypasses the insulation.
  6. Do the small spaces. Fill above headers, beside windows, at rim joists and in corners. These are skipped most often.

Faced Batts

The kraft or foil facing on a batt is a vapor retarder. Staple it as the plan shows. Many installers staple to the stud faces, for a more continuous seal, and some drywall crews prefer inset stapling, so ask first.

Facing is combustible, so do not leave faced insulation exposed in living spaces, basements or attics. It must be covered by a fire-rated material such as drywall, unless the product is rated for exposure.

Adding to attic insulation? Use unfaced batts. A facing in the middle of insulation traps moisture.

Blown-In Insulation

Attics

  1. Air seal the attic floor first.
  2. Install baffles in every rafter bay at the soffit before blowing. Baffles (ventilation chutes) keep insulation out of soffit vents, so air can flow from eave to ridge. That airflow removes moisture and helps prevent ice dams.
  3. Build a dam around the attic hatch. Keep insulation away from non-IC-rated fixtures, chimneys and flues, as code and the fixture require.
  4. Mark depth with rulers on the trusses.
  5. Set up the machine and blow an even layer to depth.
  6. Measure depth at multiple points, at least six across the attic. Depth is often thinner at the eaves.
  7. Compare your bag count with the manufacturer's chart. Depth alone does not prove coverage, because fluffing the material can fake it.

Retrofit Walls

Cellulose is the material most commonly blown into existing wall cavities. Workers drill holes from inside or outside, insert a fill tube, and pull it back as the cavity fills.

The target density for dense pack is 3.5 pounds per cubic foot, at which point cellulose stops most air movement. Listen to the machine. When it labors or stalls, the cavity is full and at density. If it blows freely, you are not there yet. Plug the holes and patch.

Stop and report these conditions in an older house. Do not cover or disturb them until a qualified person has checked:

  • Knob-and-tube wiring.
  • Vermiculite in an attic. It can contain asbestos.
  • Signs of leaks or rot.

Spray Foam

Spray foam is usually installed by trained specialty crews. Two chemicals mix at the gun, react and expand.

Property Open-cell Closed-cell
R-value per inch R-3.5 to R-3.7 R-6.0 to R-7.0
Density About 0.5 lb per cubic foot About 2 lb per cubic foot
Moisture Lets vapor pass Blocks vapor at about 1-1/2 inches

Closed-cell foam has a higher R-value per inch, and it also serves as a vapor retarder. Open-cell foam costs less and absorbs more sound.

Apply closed-cell foam in lifts of no more than about 2 inches per pass, or the limit shown by the manufacturer. Thick passes overheat, cure poorly, and can even catch fire.

Most building codes require a 15-minute thermal barrier, typically 1/2-inch drywall, over foam in occupied spaces. Attics and crawl spaces may allow an ignition barrier instead.

Warning: The isocyanate in spray foam is a strong respiratory sensitizer. Sprayers wear supplied-air respirators and full protective suits. Others must leave the area. Only return when the maker's re-entry time has passed, usually at least 24 hours.

Rigid Foam

Rigid foam goes under slabs, on foundation walls, at rim joists and as continuous insulation outside wall sheathing. Stagger the layers, tape seams with compatible tape, and fasten through the foam into the framing with long screws. Flash windows and doors through the foam to the water barrier behind it, as the plan shows.

Moisture and Vapor Retarders

A vapor retarder limits water vapor passing through a wall, so that it cannot condense inside. In winter, warm indoor air carries moisture toward the cold side. In summer, hot, humid air can drive it inward.

Class Rating Examples
I 0.1 perm or less Polyethylene, foil
II Over 0.1 to 1.0 perm Kraft facing
III Over 1.0 to 10 perms Latex paint on drywall

In cold climates, the vapor retarder goes on the interior (warm) side. In hot, humid climates, avoid an interior sheet of plastic, because air conditioning can pull moisture into it. Mixed climates usually use materials that can dry in both directions. Follow the local code.

Never put a vapor retarder on both sides of a wall. Moisture that gets in has no way out, and the result is condensation, mold and rot.

Air leaks carry far more moisture into walls than vapor diffusion, so air sealing is also moisture control.

Attics and Crawl Spaces

Attics need ventilation at the eaves and ridge unless they are built as unvented assemblies. Ice dams form when heat escapes, melts snow on the upper roof, and water refreezes at the cold eave. Air sealing, insulation and clear baffles prevent them.

Current best practice for crawl spaces is to insulate the walls and seal the space as conditioned space, with a ground vapor retarder, rather than vent it and insulate the floor. Follow the plan and local code.

Mold and Wet Insulation

Find and fix the moisture source first. Then remove and replace moldy insulation. Do not cover or paint over mold.

Working Safely

  • Fiberglass and mineral wool. Wear long sleeves, gloves, safety glasses and a dust mask or respirator. To wash skin, rinse with running water and mild soap, using a washcloth. Do not rub or scratch. See a doctor if irritation does not go away.
  • Cellulose. Dust can be heavy. Wear a respirator and eye protection.
  • Attics. Walk only on joists or decking, since a ceiling will not hold you. Watch for roofing nails.
  • Heat. Attics can exceed 140°F in summer. Work early in the day, take frequent breaks in a cool place, and drink about 8 ounces of water every 15 to 20 minutes. Do not chug large amounts at once. Stop and tell someone if you feel dizzy, confused or sick.

Check Your Understanding

1. A wire runs through the middle of a wall bay. What do you do with the batt?

Split it into two layers, with one behind the wire and the other in front.

2. A coworker packs an R-19 batt into a 2x4 wall to get extra R-value. What happens?

It compresses, so it delivers much less than R-19, around R-12 or R-13. Use a batt that fits the bay.

3. You are about to blow an old attic and see open gaps around pipes and wires. Can you blow now and seal later?

No. Insulation will cover the leaks. Seal first.

4. You find soft, gray-brown pellets in an old attic. What do you do?

Stop and report it. It could be vermiculite, which can contain asbestos. Do not disturb it.

5. In a cold climate, a wall has poly on the inside. The builder wants foil-faced foam sheathing outside, too. What should you ask?

Whether the assembly is designed to dry. Two vapor barriers can trap moisture. Ask for the design to be checked.

Key Takeaways

  • Air seal first, because insulation does not stop air leaks.
  • Fill every cavity with no gaps, voids or compression.
  • Split batts around wires, and cut them around boxes.
  • Install baffles before blowing attic insulation, and check depth at six or more points.
  • Dense-pack cellulose must reach 3.5 pounds per cubic foot.
  • One vapor retarder, never two. In cold climates, it goes on the warm side.