Ductwork Fabrication & Installation

15 min read Training Guide

Choose duct materials, lay out, cut and seam sheet metal, build fittings, seal and insulate joints, size ducts and hang them to code.

Table of contents

Ductwork carries conditioned air to rooms and brings it back. Poor ductwork wastes energy, causes comfort complaints, makes noise and shortens equipment life. A good installer knows the materials, can make a fitting from flat stock and seals every joint before the ceiling closes. This guide covers the work in the shop and on the job, along with the numbers behind it.

What You Will Be Able to Do

  • Choose the right duct material and sheet metal gauge.
  • Lay out, cut and seam a rectangular duct section.
  • Join sections and choose fittings that limit pressure loss.
  • Seal, test and insulate a duct system.
  • Size a branch duct and check its velocity.
  • Support duct at the right spacing.

Trunk and Branch Layout

Most systems use a trunk and branch layout. A large main duct leaves the air handler, and smaller ducts branch off to each room. A takeoff is the fitting that makes each branch connection. Return ducts bring air back to the equipment.

Standards for this work come from SMACNA, the Sheet Metal and Air Conditioning Contractors' National Association, and from local mechanical codes.

Duct Materials

Material Best use Watch out for
Galvanized sheet metal Trunks, commercial work Heavier, needs insulation in unconditioned spaces
Flexible duct Short branch runs Sagging and kinks
Fiberglass duct board Quiet systems Easily damaged, needs a smooth sealed face
Spiral round duct Long runs and exposed work Takes more height than rectangular duct

Round versus rectangular. Round duct has lower friction loss for the same airflow and uses less material. It is also stronger and quieter. Rectangular duct fits better in shallow spaces.

Sheet Metal Gauge

A lower gauge number means thicker metal. Residential duct is most commonly 26 gauge. A common simplified table for rectangular duct, based on SMACNA, looks like this:

Largest side Gauge
Up to 12 inches 26
13 to 30 inches 24
31 to 60 inches 22
61 to 84 inches 20
Over 84 inches 18

Actual gauge also depends on pressure class and reinforcement, so follow the job specification.

Flexible Duct Rules

  • Pull it tight. Sagging and compression greatly increase resistance, and a poor flex run can have 3 to 5 times the pressure loss of a rigid one.
  • Support it at no more than about every 5 feet, and within 3 feet of connections.
  • Keep runs short. Local limits are often 14 to 25 feet.
  • Avoid sharp bends. Use a rigid elbow if the turn is tight.
  • At the collar, seal the inner liner with mastic and fasten it with a drawband or zip tie. Mastic stops air leakage, and the band holds the liner on the collar. You need both.

Fiberglass Duct Board

Duct board comes in 1-inch or 1-1/2-inch panels, with built-in insulation and good sound control. It is sealed with UL 181 tape and is not suited to kitchen exhaust or high-velocity use. The inner face must stay smooth and sealed.

Reading the Plans

Before you cut any metal, study the drawings for:

  • Duct routing and sizes.
  • CFM at each takeoff.
  • Fitting types.
  • Pressure class, which sets gauge, reinforcement and sealing. Residential is often 1 in. w.c., and commercial ranges from 2 to 10 in. w.c.
  • Insulation requirements.

Layout and Cutting

Stretch-out is the width of the flat pattern. For a straight section, add all four sides, then add seam allowances. On a Pittsburgh lock, add about 1-1/4 inches for the pocket and about 3/8 inch for the hook.

Worked example: a 12 by 8-inch duct has sides of 12 + 8 + 12 + 8 = 40 inches. With 1-1/4 inches for the pocket and 3/8 inch for the hook, the stretch-out is about 41-5/8 inches.

Fittings use pattern development methods. Parallel line layout works for elbows, radial line layout works for cones, and triangulation works for square-to-round transitions. Shops often use CNC plasma tables, but hand layout helps you check their output and make fittings in the field.

Aviation snips are color-coded. Red cuts left, green cuts right and yellow cuts straight. Use a notcher for corners, a shear for long straight cuts, and a plasma cutter for heavier gauge.

Warning: Cut sheet metal edges are like razors. Keep cut-resistant gloves and safety glasses on, and keep your hands clear of shears, brakes and roll formers. Machine guards stay in place.

Forming and Seams

A sheet metal brake forms straight bends, and a hand brake forms edges for drive cleats and S-locks. Metal springs back slightly, so bend a bit past your target.

Pittsburgh lock seam. This is the common longitudinal seam that closes a rectangular section.

  1. Form a pocket on one edge, using a Pittsburgh machine or a hand seamer.
  2. Form a 90-degree hook on the other edge.
  3. Insert the hook in the pocket.
  4. Hammer the pocket flat to lock it.

Snap-lock seam. This seam is quicker to assemble but not as strong. It suits low-pressure residential work.

Joining Sections

Joint How it works Use
S-slip and drive cleat S strips on two sides, drive cleats folded over the other two Small to medium low-pressure duct
TDC or TDF flange Formed flanges bolted with a gasket between them Standard commercial duct
Companion angle Angle iron bolted around the ends High-pressure and large ducts

An S-slip and drive joint is not airtight when assembled. Seal it with mastic.

Fittings

Elbows. Airflow separates in sharp turns. A radius elbow gives the smoothest turn. Many are built with a centerline radius of 1.5 times the duct width. Keep the throat radius at least half the duct width. A square-throat elbow needs turning vanes, which guide air around the corner and reduce pressure loss. Without vanes, it has a very high pressure loss.

Transitions. A transition changes duct size, shape or both. Keep it gradual. Common limits are 15 degrees per side for an expansion and 30 degrees per side for a reduction.

Branches. A tee is a square branch with higher pressure loss. A wye is a 45-degree branch with lower loss. A conical takeoff is a good choice for round branches.

Volume dampers. Put a manual damper in each branch so the system can be balanced. Add them at fabrication, not later.

Sealing

Sealing keeps conditioned air from leaking into unconditioned spaces. Residential ducts often leak 20 to 30% of their air when they have not been sealed well.

Sealant Notes
Water-based mastic Best for permanent joints. Use mesh tape for gaps wider than about 1/4 inch
UL 181 foil tape Must be listed for the duct type, on clean and dry surfaces
Aerosol sealing Injected from inside to seal existing duct systems, with special equipment

Never use hardware-store cloth duct tape. It dries, cracks and peels off in 1 to 5 years, and all those joints leak again.

Testing for Leaks

A duct leakage test uses a calibrated fan and gauge to pressurize the sealed system. Leakage is measured at 25 Pa, which is 0.1 in. w.c., and is reported as CFM25. Residential energy codes commonly limit total leakage to 4 CFM25 per 100 square feet of conditioned floor area. Check your local code.

Insulation

Duct insulation stops heat gain or loss, and it prevents condensation in unconditioned spaces.

  • Duct wrap: fiberglass blanket with an outer foil facing. Seal all seams with tape so humid air cannot reach cold metal.
  • Rigid board: commercial rectangular duct.
  • Internal liner: adds sound control and insulation. Install the smooth, sealed face toward the airflow, so it resists erosion and mold growth in the airstream.

Recent IECC residential editions call for R-8 on attic ducts 3 inches and larger and R-6 on smaller ones. Supply ducts in unconditioned spaces in cold climates commonly get R-8. Local adoption varies, so check the code for your job.

Sizing Ducts

The basic relationship is CFM = area in square feet x velocity in FPM.

Equal friction is the most common residential method. You pick a friction rate, typically about 0.08 in. w.c. per 100 feet, then use a duct calculator to size each section. Static regain is used for larger commercial systems.

Location Velocity guideline (FPM)
Residential main trunk 700 to 900
Residential branch 500 to 700
Supply registers 500 to 750
Return grilles 300 to 500
Commercial main trunk 1,200 to 2,000
Commercial branch 800 to 1,200

Worked example: an 8-inch round branch carries 200 CFM. The radius is 4 inches, or 4/12 of a foot. Area = 3.14 x (4/12) x (4/12) = about 0.35 square feet. Velocity = 200 / 0.35 = about 570 FPM. That is inside the branch range.

Total external static pressure (TESP) is the combined resistance the blower must overcome. Residential systems commonly design for about 0.5 in. w.c., and most residential air handlers are rated to about 0.8 in. w.c.

Supports

Duct Maximum spacing
Horizontal rectangular 10 feet, and 8 is better
Horizontal round 12 feet
Flexible 5 feet, and within 3 feet of connections
Vertical risers At each floor, up to 15 feet

Use strap hangers on most rectangular duct, trapeze hangers on large or grouped duct, and saddles on round duct. Add support at heavy fittings. In seismic zones, add bracing per SMACNA guidelines, and flexible connections at equipment.

Job Site Safety

  • Wear gloves, eye protection and hearing protection around shop equipment.
  • Lift large sheets with two people.
  • Cap duct openings and sharp edges so others do not get cut.
  • Wear long sleeves and a respirator around fiberglass.
  • Use ladders and lifts correctly. OSHA construction rules require fall protection above 6 feet.

Common Mistakes

Mistake What it costs
Saying you will seal it later It never gets sealed, and leakage stays
Sagging or kinked flex Rooms get far less air
Undersized return Airflow is low across the whole system
No volume dampers The system cannot be balanced
Leaks in attic duct Conditioned air goes outdoors
No fire damper at a rated wall or floor A failed inspection, and a fire risk

Check Your Understanding

A 36-inch-wide rectangular duct needs to be made. Which gauge does the simplified table call for? 22 gauge.

A square-throat elbow has no vanes, and the room served has poor airflow. What should you do? Add turning vanes, or use a radius elbow.

You need 100 CFM through a 6-inch round duct. What is the velocity? Area = 3.14 x (3/12) x (3/12) = about 0.196 square feet. Velocity = 100 / 0.196 = about 510 FPM.

A flex run has been connected with a drawband, but no mastic. Is the job finished? No. The band holds it on, but mastic seals the air leak.

Key Takeaways

  • Use galvanized metal for trunks, and keep flex short, tight and supported.
  • Pittsburgh seams close rectangular duct, and S-slips and drives join sections.
  • Radius elbows and turning vanes keep pressure loss low.
  • Seal every joint with mastic or listed foil tape, never cloth tape.
  • Size ducts with CFM, velocity and friction rate, and keep TESP within the equipment's rating.
  • Support duct at the right spacing, and protect yourself from sharp edges and falls.