Low-Slope Roof Systems
Tell TPO, EPDM, PVC and modified bitumen apart, understand how their seams are made and tested, keep water moving to drains, and inspect and patch a low-slope roof without making it worse.
Table of contents
A low-slope roof does not shed water by overlapping pieces the way shingles do. It holds water out with one continuous waterproof sheet, called a membrane, so every seam, patch and flashing has to be sealed like a boat hull. Porches, additions, garages, apartment buildings and almost every store and warehouse have one. The work is different from shingling, the tools are different, and some of it, such as torch work and hot-air welding, needs product training before you do it alone.
This guide is an introduction to the common systems, how they fail and how they are repaired. Each membrane maker publishes its own installation details, and a warrantied roof may need the maker's certified contractor for any repair. The 2021 International Residential Code (IRC) covers these roofs in Section R905, and commercial buildings fall under the International Building Code.
What You Will Be Able to Do
- Identify the four common low-slope membranes and how each is attached and seamed.
- Explain why drainage matters more than anything else on a low-slope roof.
- Check a welded seam and recognize a bad one.
- Inspect a roof and match each defect to a repair.
- Stay safe at roof edges, skylights and around torches and solvents.
What Counts as Low-Slope
| Measure | Rule |
|---|---|
| Lowest slope for asphalt shingles (IRC) | 2:12 |
| Lowest design slope for modified bitumen, EPDM, TPO and PVC (IRC) | 1/4:12, about a 2 percent slope |
| OSHA "low-slope roof" for fall protection | 4:12 or less |
A 1/4:12 slope drops a quarter inch for every foot. Over 40 feet, that is only 10 inches, which is why these roofs look flat.
Fall protection. On low-slope roofing work 6 feet or more above a lower level, OSHA requires guardrails, safety nets, personal fall arrest, or a warning line combined with one of those or a safety monitor (1926.501(b)(10)). Skylights count as holes. They need covers, guardrails or fall arrest (1926.501(b)(4)). People have died stepping on or sitting on a skylight.
Layers of a Low-Slope Roof
From the bottom up, a typical commercial roof has:
- Deck: steel, wood or concrete.
- Vapor retarder, in some climates and buildings.
- Insulation boards, often polyiso, sometimes tapered to create slope.
- Cover board, a thin, hard board that protects the insulation from foot traffic.
- Membrane, the waterproof layer.
- Flashings and edge metal at walls, curbs, drains and edges.
The membrane is held down in one of three ways: mechanically attached with screws and plates hidden in the seams, fully adhered with adhesive, or ballasted with stone or pavers laid loose on top.
The Common Membranes
| Membrane | What it is | How seams are made |
|---|---|---|
| EPDM | Synthetic rubber, usually black, sometimes white | Primer and seam tape, or splice adhesive |
| TPO | Thermoplastic sheet, usually white | Hot-air welded |
| PVC | Thermoplastic sheet, usually white or gray | Hot-air welded |
| Modified bitumen | Asphalt with rubber or plastic added, on a mat, in rolls | Torch, hot asphalt, cold adhesive or self-adhered |
Thermoset sheets such as EPDM are cured once and cannot be melted back together, so their seams are glued or taped. Thermoplastic sheets such as TPO and PVC soften with heat, so two sheets can be welded into one.
Modified bitumen comes in two main types. SBS is rubber-modified and can be torched, mopped, glued or self-adhered. APP is plastic-modified and is usually torch-applied. Most mod-bit roofs have a base sheet plus a mineral-surfaced cap sheet.
Seams
A seam is the weakest line on the roof. Most low-slope leaks start at a seam, a flashing or a puncture.
Welding TPO and PVC
A hot-air welder blows air hot enough to melt the two sheets together. Robotic welders run long field seams. Hand welders do details and patches.
- Clean it. Dirt, dust and old membrane chalking keep the weld from fusing. Use the maker's cleaner on weathered membrane.
- Make a test weld at the start of the day and whenever the weather, sun or membrane changes. Let it cool, then peel it apart.
- Read the test. In a good weld, the sheets are fused across the full width, and pulling them apart tears the sheet or exposes its reinforcing fabric instead of separating cleanly at the seam. Two major makers call for a weld at least 1-1/2 inches wide, and another wants 2 inches for hand-welded seams. Use the width in your maker's specification.
- Weld the seam, keeping speed and heat steady.
- Probe every seam after it cools. Run a blunt probe, such as a dull cotter pin, along the seam edge with light pressure. A probe that catches or slips into the seam has found a gap.
A cold weld looks fine but did not fuse and peels apart. A burned weld is scorched or shiny and brittle. Both get cut out or covered with a welded patch, as the maker's details show.
Taping EPDM
- Clean the seam area with the maker's cleaner or primer.
- Prime both sheets and let the primer flash off, until it is dry to the touch.
- Apply seam tape to the lower sheet, then lay the upper sheet onto it.
- Roll the seam firmly, across and then along it.
Dust, moisture or skipped primer is the usual cause of an EPDM seam that opens.
Torching Modified Bitumen
Torch work melts the back of the roll with a large propane torch as it is rolled out. It is hot work, and roofs have burned down from it. Fires often start out of sight, in a gap at a wall, under a curb or in wood blocking, and smolder for hours.
- Do not torch until you are trained and your employer authorizes you. The National Roofing Contractors Association runs a torch safety program called CERTA that many insurers and owners require.
- Never point a torch into a gap, an opening or at wood. Use cold-applied or self-adhered materials at those details.
- Keep a fire extinguisher within reach of every torch.
- Keep a fire watch after the last torch is off. The CERTA program calls for two hours. Follow your employer's and the owner's hot work permit, which may set a different time.
Drainage
Water that stays on a low-slope roof finds every weak seam, adds weight, and wears the membrane out early. The National Roofing Contractors Association treats water still standing 48 hours after a rain as a problem, called ponding.
Water leaves a low-slope roof through:
- Interior drains, with a strainer on top and the membrane clamped under a ring.
- Scuppers, openings through a parapet wall that drain into a downspout.
- Gutters at an open roof edge.
Where parapets would trap water if the main drains clogged, codes require secondary (overflow) drains or scuppers set higher than the main ones. If an overflow is running, the main drain below it is clogged.
Crickets and tapered insulation steer water around curbs and toward drains.
Keep drains and strainers clear of leaves, gravel and trash on every visit. A clogged drain can turn a roof into a pond in one storm.
Flashings and Penetrations
The membrane turns up walls and curbs as base flashing, to the height the maker's detail calls for, and is capped by counterflashing or a termination bar with sealant. Penetrations such as pipes get prefabricated boots, or field-wrapped flashings, made of the same membrane family. A pitch pan, a metal collar filled with sealant around an odd-shaped penetration, needs regular checking and topping off, so it is a last resort.
Inspecting and Repairing
| What you find | Likely cause | Repair |
|---|---|---|
| Open or lifting seam | Cold weld, dirty seam, or aged adhesive | Clean and reweld, or cover with a patch |
| Puncture or cut | Dropped tool, foot traffic, hail | Patch of the same membrane family |
| Blister in mod bit | Trapped moisture or air | Cut, dry and patch as the maker shows |
| Membrane pulling at walls or curbs | Shrinkage in aged EPDM | Add membrane or flashing per the maker |
| Ponding | Clogged drain, sagging deck, low area | Clear the drain, report the low area |
| Soft spot underfoot | Wet insulation under the membrane | Report it. Wet insulation must be found and replaced |
| Cracked flashing at a curb | Movement, aging | Strip in new flashing |
Patching rules:
- Clean the area well past the damage, using the maker's cleaner.
- Cut the patch to extend past the damage on all sides by the amount the maker's details require.
- Round the patch corners. Square corners catch and peel.
- Weld, tape or adhere the patch with the maker's materials for that membrane.
Do not use asphalt roof cement on EPDM, TPO or PVC. It does not bond well to TPO or EPDM, and it damages PVC. Use the membrane maker's repair products.
Working Safely
- Stay back from unprotected edges and know where every skylight and roof hatch is.
- Primers, cleaners and adhesives give off flammable vapors. Read the Safety Data Sheet, keep ignition sources away, and work with the wind at your back.
- White membranes reflect sun and heat. Wear sunglasses rated for UV, sunscreen and a hat, and drink water.
- Wet, frosty or dusty membrane is slick.
- Wind lifts loose sheets like sails. Weigh down rolls and cut pieces.
- Walk on walkway pads where they exist, and do not drag equipment across the membrane.
Check Your Understanding
1. A test weld on TPO peels apart cleanly at the seam with little effort. What does that tell you, and what do you do?
It is a cold weld that did not fuse. Adjust the heat or speed, clean the sheet, and make another test weld before you weld any seam.
2. You find water standing in the same corner of a roof two days after a storm, and the drain there is covered in leaves. What do you do?
Clear the strainer and drain, then check that the water drains. Report the ponding if water still stands, because the deck or insulation may have settled.
3. A coworker wants to seal a cut in a PVC roof with a can of asphalt roof cement. What do you tell them?
Asphalt damages PVC. Clean the area and weld on a PVC patch with rounded corners.
4. You finished torching a cap sheet at a parapet wall at 3 p.m. When can the fire watch end?
Not before the time set by the hot work permit and your training. Under the CERTA program, that is two hours after the last torch was turned off, so no earlier than 5 p.m.
Key Takeaways
- Low-slope roofs rely on one continuous membrane, so every seam and flashing must be sealed.
- The IRC's lowest design slope for these membranes is 1/4:12.
- TPO and PVC are welded, EPDM is taped or glued, and mod bit is torched, mopped, glued or self-adhered.
- Make a test weld every day and probe every welded seam.
- Keep drains and strainers clear. Water standing 48 hours after rain is a problem.
- Torch only with training, never into gaps, and keep a fire watch after the last torch is off.