Skip to content
Skills / Hydraulics & Pneumatics / Fluid Power for Maintenance Technicians / Reading P&IDs for Industrial Workers
Hydraulics & Pneumatics

Reading P&IDs for Industrial Workers

15 min read Training Guide

Read a piping and instrumentation diagram, from equipment, line tags and valves to instrument bubbles, control loops, relief devices and tracing an isolation.

Table of contents

A piping and instrumentation diagram (P&ID) is the map of a process plant. It shows the equipment, the pipes that connect it, the valves, the instruments and the way they control the process. Operators use it to work out why an alarm went off. Mechanics use it to plan a repair, instrument techs use it to trace a loop, and safety staff use it to plan an isolation. If you work in a refinery, chemical plant, food plant, pharmaceutical plant or water treatment plant, you will see one often. You can read one once you know how the symbols and tags work. Most of what looks complicated is just repetition.

What You Will Be Able to Do

  • Say what a P&ID shows, and how it differs from other drawings.
  • Decode equipment tags and line numbers.
  • Read an instrument tag such as TIC-118, and tell where the device is mounted.
  • Find a valve's fail position, and explain why it matters.
  • Trace a control loop and a process line from start to finish.
  • Use a P&ID to list the isolation points for a job.

What a P&ID Shows

A P&ID shows the process logic: what flows where, what measures what and what controls what. It is not drawn to scale, and it does not show where things sit in the plant.

Drawing What it shows
P&ID Process piping, equipment, valves and instruments
One-line diagram Electrical power distribution, from source to loads
Electrical schematic How a control circuit works
Plot plan or 3D model Where equipment physically sits
Isometric The route of a pipe, for fabrication

The instrument symbols come mostly from the standard ISA-5.1, but plants and engineering firms make their own changes.

Read the Legend First

Every set has a legend, usually on the first sheets. It defines equipment symbols, line types, valve symbols, instrument symbols and the line numbering format. Do not guess at a symbol. Read the legend for your plant, because a symbol can mean something else on a different site.

Equipment

Equipment is usually tagged with a letter or two and a number.

Tag example Meaning How it is usually drawn
P-101A Pump 101, unit A Circle with a discharge point
C-501 Compressor 501 Larger circle or wedge shape
E-302 Heat exchanger 302 Circle or shell with tube lines
V-410 Vessel 410 Tall or long rounded shape
TK-205 Tank 205 Cylinder from the side

P-101A and P-101B are usually a pair, with B as the installed spare. Tag letters vary by site.

Lines

Line Tags

A line number packs in a lot of information. A tag such as 4"-H2-101-A1B could mean:

  • 4" is the nominal pipe size.
  • H2 is the service, here hydrogen.
  • 101 is the line's number in the unit.
  • A1B is the pipe spec, which sets material, pressure rating and more.

The format differs by project, and the pipe spec sheet tells you what the last part means.

Line Types

Line Usual meaning
Thick solid Main process line
Thin solid Secondary process or utility line
Dashed Electrical signal
Line with paired slashes Pneumatic signal
Line with small circles Data or software link
Line with an X Capillary tube

The last four are instrument signals, not pipes. Check the legend, since older drawings can differ.

Valves

Most valve symbols start with a bowtie shape, then add a detail. The legend shows the exact versions.

Valve Typical use
Gate Full open or closed block valve
Globe Throttling or flow control
Ball Quick open or close, tight shutoff
Butterfly Large lines
Check Flow in one direction only
Plug Quarter-turn block or throttling service
Needle Fine control on small lines

A shape on top of the valve shows how it is operated: by hand, by a motor, by a diaphragm or piston using air, or by a solenoid.

Fail Position

An automatic valve needs air or power. If that is lost, it goes to a set position:

Mark Meaning
FC Fail closed
FO Fail open
FL Fail last, staying where it was
FI Fail indeterminate, with no set position

This choice is a safety decision, made when the process was designed. A feed valve to a reactor is usually FC, so that feed stops when air is lost. A cooling water valve is usually FO, so that cooling keeps going. If you change or work on one of these valves, think about what happens when you remove its air supply, because it will move.

Instruments

Instruments appear as circles, called bubbles, with a tag inside. The first letter is what is being measured. The following letters say what the device does. The number is the loop.

First letter Measures Following letter Function
F Flow I Indicate
P Pressure T Transmit
T Temperature C Control
L Level R Record
A Analysis A Alarm
S Speed S Switch
W Weight V Valve

H and L after a switch or alarm mean high and low.

Tag Meaning
TIC-118 Temperature indicating controller, loop 118
FT-201 Flow transmitter, loop 201
FIT-226 Flow indicating transmitter, loop 226
FV-201 Flow control valve, loop 201
PSH-331 Pressure switch, high, loop 331
TAH-412 Temperature alarm, high, loop 412
LSL-107 Level switch, low, loop 107

Position matters. In TIC, the T comes first, so it means temperature. In FT, the T comes after the first letter, so it means transmit.

Where the Instrument Is

Symbol Location
Plain circle In the field
Circle with a solid line across it Main control room or panel, within the operator's reach
Circle with a dashed line across it Behind a panel, not normally reached by the operator
Circle inside a square Shared display, such as a control system screen

Check the legend, because some sites use their own rules.

Control Loops

A control loop has a sensor, a controller and a final element, usually a valve.

Worked example: Temperature at an exchanger outlet.

  1. TT-118 measures the outlet temperature, and sends a signal.
  2. TIC-118 compares the reading to the setpoint.
  3. TV-118, on the steam line, opens or closes to bring the temperature back.

All three share the number 118, so you can find them on the page. If the loop breaks, the symptom points to the fault. A frozen reading suggests the transmitter. A controller output that climbs to 100 percent with no change in the process suggests a stuck valve or a lost supply.

Relief Devices

Relief devices are the last line of defense against overpressure.

  • Pressure safety valve (PSV): opens at a set pressure, and is tagged like PSV-250. The P&ID often shows the set pressure.
  • Rupture disk: a thin membrane that bursts at a set pressure, often fitted upstream of a PSV in corrosive service.
  • Relief header: the pipe that takes the discharge to a flare or another safe place.

Follow each relief line to see where it goes. Block valves near relief devices are controlled closely, so treat them with care.

Tracing a Process

This is the main skill. Print a copy and use a highlighter.

  1. Pick a start point, such as a vessel or pump.
  2. Follow the line in the direction of the flow arrow.
  3. Write down each valve as you pass it.
  4. Write down each instrument along the way.
  5. Mark each branch, such as a drain, bypass or tie-in.
  6. Note each control valve and its loop.
  7. Stop at the next vessel, and pick up from there.

Then walk the line in the field, and check that what you wrote matches what is installed.

Using a P&ID for Isolation

Before you work on equipment, trace every path that could bring energy or material to it.

Isolation point What to look for
Upstream block Valve just before the equipment
Downstream block Valve just after the equipment
Bleed or drain Way to relieve what is trapped
Electrical disconnect Motor starter or disconnect
Instrument air Supply to the actuator or solenoid
Utility connections Steam, nitrogen and water tie-ins
Bypass lines Lines that go around your block valve

On hazardous service, double block and bleed is common. That means two block valves closed and locked, with a bleed between them locked open, so that any leak past the first valve goes somewhere safe. Check with a gauge that the space between them stays at zero. Blinds are often used for the highest-risk isolations.

Worked example: You need to open pump P-101A while P-101B stays running.

  1. Find the suction and discharge block valves for P-101A.
  2. Look for a shared line that stays live from P-101B.
  3. Find the drain and vent on the pump casing.
  4. Find the motor disconnect.
  5. Check for seal flush lines and any instrument taps.
  6. List each one, with its tag, on the isolation plan.

Your site's lockout procedure sets the rules. The P&ID only helps you find the points, so confirm them in the field.

Revisions and Redlines

Drawings fall behind reality. A field change during a turnaround may not make it back to the master copy before startup.

  • Check that you have the current revision.
  • Confirm in the field, because a valve on the drawing may have been removed or replaced.
  • If the field and the drawing disagree, stop and ask before you rely on either.
  • Mark the difference on a copy, and send the redline to document control.

Out-of-date drawings have contributed to serious process incidents, so treat a mismatch as a safety issue.

Common Mistakes

Mistake What it costs Better habit
Skipping the legend Misreading a symbol Read it for each site
Assuming the drawing is current Isolating the wrong thing Walk it down in the field
Forgetting bypasses and utilities A line that is still live Trace each connection
Ignoring fail position A valve that moves when air is cut Check FC and FO first
Reading a signal line as a pipe A wrong trace Check the line type

Check Your Understanding

1. You see PIC-310 in a circle with a solid line across it. What is it, and where?

A pressure indicating controller for loop 310, located in the main control room or panel.

2. A valve on a fuel line is marked FC. What happens if instrument air fails?

It closes, which stops the fuel.

3. TIC-205 shows the setpoint at 150 degrees, the reading is stuck at 120 and the output sits at 100 percent. Where might you look?

The valve or its air supply, or the steam source. The controller is calling for more, but the process is not responding.

4. You plan to isolate a vessel and find two block valves on the inlet, but the drawing also shows a small nitrogen tie-in. What should you do?

Include it. The nitrogen line can bring in gas and displace air. Isolate and lock it as well, and confirm it in the field.

Key Takeaways

  • A P&ID shows process logic, not physical layout or electrical power.
  • Read the legend for each site.
  • In an instrument tag, the first letter is the measurement, and the rest give the function.
  • FC and FO show what a valve does when air or power fails.
  • A control loop has a sensor, a controller and a final element with the same number.
  • Trace every path before isolation, and confirm it in the field.