Refrigerant Recovery and Recycling

10 min read Training Guide

Set up a recovery machine, run vapor and push-pull recovery, handle cylinders safely and finish the job with no refrigerant left behind.

Table of contents

Refrigerant has to come out before you open a sealed system, replace a major part or scrap a unit. Recovery is mostly simple, but it can go wrong in dangerous ways, such as an overfilled cylinder, a mixed tank or refrigerant left trapped in the oil. Federal rules set how far you must go, and this guide shows how to do the work: setting up the machine, picking a method and handling the cylinder.

What You Will Be Able to Do

  • Name the parts of a recovery machine.
  • Set up hoses and cylinders so air stays out.
  • Run vapor recovery.
  • Run push-pull recovery on a large charge.
  • Weigh a cylinder and stop at the right fill level.
  • Confirm that recovery is complete.

Recover, Recycle, Reclaim

Recovery removes refrigerant into a container. Recycling cleans it for reuse in the same owner's equipment. Reclaiming sends it off-site to be reprocessed to purity standards so it can be sold to any owner. Most service work stops at recovery, and the shop sends full cylinders to a reclaimer.

Inside a Recovery Machine

Part What it does
Compressor Draws refrigerant from the system and pushes it to the cylinder
Condenser Cools hot gas into liquid
Inlet filter-drier Catches dirt, moisture and acid before the compressor
High-pressure cutout Stops the machine if cylinder pressure gets too high
Inlet and outlet valves Control flow in and out of the machine
Purge setting Clears the machine and hoses between jobs

A machine must be certified under EPA rules, and it must be listed for the refrigerant you are recovering. Check for A2L ratings before using it on R-32 or R-454B.

Keep a simple log of hours, filter changes and any oil changes. A clogged filter makes the machine slow, and a burned-out system can destroy a recovery compressor.

Before You Start

  1. Read the data plate for refrigerant type and charge.
  2. Check the recovery cylinder. Look at the hydrostatic date, look for rust or dents, and confirm it is rated for the refrigerant.
  3. If the cylinder has been emptied or is new, pull a vacuum on it so air does not end up in the recovered refrigerant.
  4. Put the cylinder on a scale, and zero it or note the starting weight.
  5. Wear eye protection and suitable gloves. Ventilate the space.
  6. Use hoses with low-loss fittings. Remove Schrader cores with a core tool when you can, to speed the flow.
  7. Pull hoses into a vacuum, or purge them through the machine, so air does not get in.

Compare the refrigerant label on the system with any gauge reading. If you are not sure what is in the system, use a refrigerant identifier or a separate cylinder.

Vapor Recovery

Vapor recovery works for most residential and light commercial systems.

  1. Connect a hose from the system to the machine's inlet. Connect both the high and low sides if you can.
  2. Connect a hose from the machine's outlet to the cylinder's vapor valve.
  3. Open the valves in the order given in the machine's manual.
  4. Start the machine, and watch the pressures.
  5. Keep watching the scale so the cylinder stays under its limit.
  6. Run until the system reaches the required level.
  7. Shut off the system side, then finish clearing the machine into the cylinder.
  8. Wait several minutes and watch for a pressure rise.

If pressure rises, refrigerant is still boiling out of the oil or a closed-off section. Run the machine again.

Push-Pull Recovery

Push-pull moves liquid and is much faster on large charges. A charge of about 15 lb or more is a common minimum. Smaller systems do not have enough liquid to make it worthwhile.

  1. Connect a hose from the system's liquid service port to the cylinder's liquid valve.
  2. Connect the cylinder's vapor valve to the machine's inlet.
  3. Connect the machine's outlet to the system's vapor port.
  4. Open all the valves and start the machine.
  5. The machine pulls vapor from the cylinder and pushes it into the system. That lowers cylinder pressure, raises system pressure and pushes liquid into the cylinder.
  6. Watch the scale closely. Liquid moves fast, and it can keep siphoning after you stop the machine.
  7. Close the liquid valve before the cylinder reaches its limit.
  8. When liquid stops moving, change to vapor recovery to finish.

Push-pull does not work well if the system has no standing liquid, such as a system with no receiver and refrigerant spread out across coils.

Cylinder Handling

  • Fill to 80% by weight, and use a scale every time.
  • Recovery cylinders have a gray body and a yellow top.
  • Use one refrigerant per cylinder. Mixed refrigerant may not be reclaimable, and it costs far more to dispose of.
  • Do not put recovered refrigerant in a disposable cylinder.
  • Label the cylinder with the refrigerant, the date and the job.
  • Check that the 5-year hydrostatic test is current.
  • Store and move cylinders upright and secured, with valve caps on, out of direct sun.

Worked example: a cylinder's label allows 40 lb of R-410A. It already holds 12 lb, and you expect to recover 30 lb. 12 + 30 = 42 lb, which is over the limit. Bring a second cylinder before you start.

To check a stored cylinder for leaks, pressurize it with a small amount of dry nitrogen, soap the valve and stem, then release the nitrogen and pull a vacuum on it. A bubble means it needs service.

Speeding Up a Slow Recovery

  • Use short, wide hoses and remove core depressors.
  • Recover from both sides of the system.
  • Change a clogged inlet filter.
  • Cool the cylinder on a hot day, such as with an ice bath around its base.
  • Warm the system gently with the indoor fan or by working in the sun, but never heat a cylinder or system with a flame.
  • If the machine trips on high pressure, check for a closed valve, a full cylinder, or air in the tank.

After Recovery

Record the amount recovered and the refrigerant type. Many jobs require this on the service ticket. A system that held refrigerant should be purged with nitrogen before you apply heat to any joint.

If the system had a burnout, treat the oil and refrigerant as contaminated. Use a separate cylinder, change the machine's filter and send the refrigerant to a reclaimer.

Before you switch to a different refrigerant, run the machine's self-purge, so the old refrigerant does not contaminate the next cylinder.

Common Mistakes

Mistake What it costs
Skipping the scale An overfilled cylinder that can rupture
Not clearing air from the hoses Air in the recovered refrigerant
Stopping at the first low reading Refrigerant left behind
Mixing refrigerants in one tank A contaminated tank that may be costly to dispose of
Using push-pull with no scale in view Liquid overfills the cylinder fast
Leaving a valve shut between the machine and the cylinder High-pressure trip or a hose burst

Check Your Understanding

You reach the target and shut down. Ten minutes later the pressure has climbed. What does that mean, and what do you do? Refrigerant is still coming out of the oil or a trapped section. Run the machine again.

A small split system holds 6 lb. Should you use push-pull? No. Use vapor recovery. Push-pull suits larger charges.

A cylinder's label allows 35 lb of refrigerant. Your scale reads 34 lb and 5 lb remain in the system. What do you do? Change to a second cylinder before you go on.

You are moving from an R-22 job to an R-410A job. What should you do with the machine? Run its self-purge and use a separate cylinder for the new refrigerant.

Key Takeaways

  • Use a certified machine listed for the refrigerant.
  • Vapor recovery fits most small systems, and push-pull is for charges of about 15 lb or more.
  • Weigh every cylinder, and stop at 80% by weight.
  • Keep one refrigerant per cylinder, labeled.
  • Wait and check for a pressure rise before you call recovery complete.