HVAC Controls & Thermostats

Thermostat Wiring Basics

10 min read Training Guide

Trace R, C, G, Y, W and O/B through a 24-volt control circuit, wire a thermostat and find out where a call for heat or cooling stops.

Table of contents

A thermostat is a set of switches. It connects 24 volts from a transformer to whichever wire asks for heat, cooling or the fan. If you know what each terminal does, you can read a wiring diagram and find out where a call for heat or cooling stops, in a few minutes. This is the most common control task in residential HVAC.

What You Will Be Able to Do

  • State what each standard thermostat terminal controls.
  • Explain why smart thermostats usually need a C wire.
  • Decide whether to install a jumper between Rh and Rc.
  • Wire a thermostat safely and test each mode.
  • Follow a call from the thermostat to the equipment with a meter.

The 24-Volt Control Circuit

A small transformer in the furnace or air handler steps line voltage down to about 24 volts AC. One side of the transformer feeds the R terminal. The other side is common, C. Every control device needs a path from R, through a switch, through its coil, and back to C.

A 3-amp or 5-amp fuse on the control board protects the transformer. If a wire shorts, that fuse blows and the thermostat often goes dead.

The Standard Terminals

Terminal Usual color What it does
R Red 24-volt power from the transformer
Rc, Rh Red Separate 24-volt feeds for cooling and heating
C Blue or black Common, the return path to the transformer
G Green Runs the indoor blower fan
Y Yellow Runs the compressor and outdoor unit for cooling
W White Calls for heat, such as a gas valve sequence or heat strips
Y2, W2 Varies Second stage of cooling or heat
O/B Orange or dark blue Controls the reversing valve on a heat pump
Aux, E Varies Auxiliary or emergency heat on a heat pump

Colors are a custom, not a rule. Trace the wire by where it lands, not by its color.

The C Wire

The C wire gives the 24-volt circuit a steady return path. Older thermostats ran on batteries or on tiny amounts of current that passed through the control circuit. A smart thermostat needs steady power for its screen and Wi-Fi radio, and most need a C wire to run reliably.

If no C wire exists, your options are:

  1. Use a spare conductor in the existing cable, if there is one.
  2. Run a new thermostat cable with enough conductors. This is the best long-term fix.
  3. Use a manufacturer's add-on adapter where it is listed for that equipment.

Rh, Rc and the Jumper

Some thermostats have separate R terminals for heating and cooling. Most homes have one transformer, so one R wire feeds both. In that case, install the jumper between Rh and Rc, or use the thermostat setting that does the same job.

A system with two separate transformers has two R wires, one for heat and one for cooling. In that case, do not install the jumper, because you would tie two power sources together.

Heat Pump Terminals

A heat pump adds a reversing valve, and manufacturers differ on when they energize it.

  • O: energizes the reversing valve in cooling. This is the most common setup, including Carrier, Trane, Lennox and Goodman.
  • B: energizes the reversing valve in heating. Rheem and Ruud use this.

Set the thermostat to match the equipment, and check the wiring diagram. A wrong setting makes the system heat when asked to cool, and the other way around.

Aux brings on backup heat alongside the compressor when the heat pump cannot keep up, or during defrost. E or emergency heat runs the backup heat alone and locks out the compressor. Use emergency heat only when the heat pump has a problem.

Wiring a Thermostat

  1. Turn off power at the breaker or the equipment switch. Confirm with a meter between R and C that the circuit is dead.
  2. Take a photo of the existing wiring, at the thermostat and at the equipment.
  3. Label each wire with the terminal it came from.
  4. Remove the old thermostat. If it is mercury, recycle it as hazardous waste.
  5. Mount the new base level. Seal the wall hole so wall drafts do not fool the sensor.
  6. Connect each wire to its terminal, and confirm each one lands on the matching terminal at the equipment.
  7. Set the correct jumper, O or B, and equipment type.
  8. Restore power, then test heat, cooling and fan-only modes. Check that the compressor delay and each stage work.

Warning: Do not connect a low-voltage thermostat to a line-voltage heater circuit, or a line-voltage thermostat to a 24-volt system. A line-voltage thermostat switches 120 or 240 volts directly, and using the wrong kind can destroy the thermostat and create a shock or fire risk.

Tracing a Call

Following the voltage shows where the problem is. Testing live circuits is work for qualified people, or a trainee under direct supervision.

  1. Set the thermostat to call for cooling, heat or fan.
  2. At the thermostat, measure from C to the called terminal. You should see about 24 volts.
  3. At the equipment, measure the same terminal to C.
  4. If you have voltage at the thermostat but none at the equipment, the wire between them is broken or shorted.
  5. If you have voltage at the equipment, check the next device in line, such as the contactor or the control board.

A common shortcut: with a known-good thermostat, a trained technician can jumper R to G at the control board. The blower should run. That proves the board and blower respond, and the thermostat or wire is the likely problem. Only do this if you have been trained, and with the right tools.

When the Fuse Blows

  1. Turn off power.
  2. Disconnect the thermostat wires from the board one at a time.
  3. Check each wire for a short to ground or to another wire.
  4. Check for a wire pinched by a nail plate or sheet metal edge. A wire that touches the outdoor unit's metal is a common cause.
  5. Fix the short before you restore power. Replace the fuse with the same rating.

Common Mistakes

Mistake What it costs
Not photographing the wiring first A long reconnect job and blown fuses
Trusting wire colors Crossed circuits
Leaving out the Rh to Rc jumper with one transformer The cooling side has no power
Wrong O/B setting Heat when you want cooling
Replacing the fuse before finding the short A second blown fuse

Check Your Understanding

A new thermostat has Rh and Rc terminals and the wall has one red wire. What do you do? Connect it to R or Rh and install the jumper between Rh and Rc.

A heat pump heats when set to cool. What is the first thing to check? The O/B setting and wiring. The reversing valve is running on the wrong convention.

You measure 24 volts at the thermostat from Y to C during a call, and 0 volts at the equipment's Y terminal. Where is the problem? The wire between the thermostat and the equipment.

A customer wants a smart thermostat, and the wall has no spare wire. What is the best long-term fix? Run a new cable with a dedicated C conductor.

Key Takeaways

  • R is 24-volt power, C is the return path, G is the fan, Y is cooling and W is heat.
  • The O/B terminal runs the reversing valve, and brands differ on when it energizes.
  • Install the Rh to Rc jumper on one-transformer systems.
  • Trace voltage from the thermostat to the equipment to find where a call stops.
  • A blown control fuse means there is a short to find.