Servicing PTAC and Window Air Conditioners

15 min read Training Guide

Clean and service PTAC units and window air conditioners, diagnose no cool, no heat, leaks and noise, and know when a sealed-system failure means a new chassis.

Table of contents

A PTAC, short for packaged terminal air conditioner, is the through-the-wall unit under the window in many hotel rooms, apartments and senior living buildings. Everything is in one box, called the chassis, which slides into a metal sleeve built into the wall. Many PTACs also heat, with an electric heat strip or as a heat pump, which is often labeled a PTHP. A window air conditioner works the same way, but sits in a window opening. Both are factory-sealed units, so most of your work is cleaning, airflow, drainage and simple electrical parts. Keep them clean and they rarely fail. Neglect them and they freeze, leak and grow mold.

What You Will Be Able to Do

  • Isolate a PTAC or window unit and handle its chassis safely
  • Name the main parts and what each one does
  • Carry out a filter clean and a full coil cleaning
  • Diagnose no cool, no heat, water leaks, noise and odors
  • Decide between a repair and a new chassis, and dispose of a unit legally

Make It Safe

Power. Most PTACs plug into a 208/230-volt receptacle under or beside the unit. Some commercial units run on 265 volts and are hardwired or use a special receptacle. Window units plug into 115 volts or, for large ones, 230 volts. Unplug the unit and keep the plug in your control, or lock out the breaker for a hardwired unit. Prove it dead before you touch any wiring.

The cord. Most plug-in room air conditioners have a test and reset button on the plug or cord. The electrical code requires a protective device like this on single-phase plug-in room air conditioners. It cuts power if the cord is damaged. Never replace it with an ordinary cord or bypass it.

Weight and edges. A PTAC chassis is heavy and its coil fins are sharp. Slide it onto a cart with a second person, and wear gloves.

Refrigerant. Most PTACs and window units are small appliances under EPA rules: factory-made, charged and sealed, with 5 pounds of refrigerant or less. Opening the sealed system takes EPA Section 608 Type I or Universal certification. Many newer units use R-32 or R-290, which are flammable, so read the label and do not puncture, cut or heat the tubing.

Know the Parts

Part Where it is What it does
Room filters Behind the front panel Catch dust before it reaches the indoor coil
Indoor coil Behind the filters Cools or heats the room air
Indoor blower wheel Behind the indoor coil Moves room air
Outdoor coil At the back, facing the exterior grille Sheds heat outdoors in cooling
Fan motor Between the two coils Often one motor with a shaft out each end, driving both fans
Slinger ring Around the outdoor fan blade Throws condensate onto the hot outdoor coil, where it evaporates
Heat strip Near the indoor blower Electric heat on most PTACs
Base pan and drain Bottom of the chassis Hold and drain condensate
Wall sleeve and grille In the wall Hold the chassis and let outdoor air pass

A little water in the base pan is normal. The slinger ring is designed to pick it up and spray it onto the outdoor coil, which helps the unit run efficiently.

Routine Service

Task How often Notes
Clean the room filters Monthly, or per your site's schedule More often in dusty or smoking rooms
Check the exterior grille Each filter clean Clear leaves, nests and debris
Check the cord and test the plug's protective device Each filter clean Replace a damaged cord with the maker's part
Clean the coils, blower wheel and base pan At least yearly More often near the coast, construction or cottonwood trees
Run heat and cool modes Before each season Catch failures before the first cold or hot day
Check the seal between chassis and sleeve Yearly Gaps let in air, water and insects

Cleaning the Filters

  1. Turn the unit off and unplug it.
  2. Remove the front panel and slide out the filters.
  3. Vacuum them, or rinse them with warm water from the clean side so dirt washes out the way it came in.
  4. Let them dry fully before you put them back. A wet filter can grow mold.

A Full Coil Cleaning

  1. Unplug the unit, or lock out its breaker. Remove the front panel.
  2. Remove the screws or brackets holding the chassis in the sleeve.
  3. Slide the chassis out onto a cart, with a helper. Take it to a cleaning area or outside.
  4. Cover the control box, the fan motor and the heat strip connections with plastic bags.
  5. Apply a coil cleaner made for aluminum coils to both coils, and let it work as its label says.
  6. Rinse both coils with a garden hose at low pressure, from the clean side out. Do not use a pressure washer. It flattens the fins and blocks the airflow you are trying to restore.
  7. Clean the blower wheel's blades, which collect dust, and scrub the base pan and drain holes.
  8. Straighten bent fins with a fin comb.
  9. Let it drain and dry. Remove the bags.
  10. While the chassis is out, check the sleeve. It should be level side to side and tilt slightly toward the outside, as its maker says. Many call for about a quarter bubble on a level. A sleeve tilted toward the room drains water onto the floor.
  11. Slide the chassis back, check its gasket or seal, fasten it, and replace the front panel.
  12. Restore power and run it in cooling and heating.

Diagnosing a PTAC or Window Unit

Symptom Likely cause What to do
Completely dead Breaker, tripped plug protector, or a failed board Check the breaker. Press reset. If the plug trips again, the cord or unit has a fault
Fan runs, air not cold Setpoint or mode, dirty coils, or a frozen indoor coil Check settings, clean filters and coils, thaw any ice
Fan runs, compressor never starts Capacitor, compressor overload, or the compressor See the capacitor steps below, then call it in
Outdoor fan not turning Failed fan motor or capacitor, or a blade hitting ice Lock out, check the blade spins freely
No heat, electric strip models Mode, the heat strip, or its high limit Test the strip and limit with the power off
No heat, heat pump models In cold weather many switch to the strip. Outdoor coil iced Check the strip, and that defrost clears the coil
Water leaking into the room Sleeve tilted inward, a clogged base pan drain, or a missing seal Level the sleeve, clear the drain, reseal
Rattling or banging Loose chassis, fan blade hitting the shroud or ice, a loose blower wheel Tighten, align, check the set screw on the blower wheel
Musty smell Dirty indoor coil, wet filter, or standing water in the base pan Clean the coil and pan, dry the filter
Burning smell at the start of heating season Dust burning off the heat strip Normal briefly. If it lasts or smokes, shut it off

Testing the Heat Strip

With the unit unplugged, find the heat strip's terminals and test its resistance. Estimate it from its rating: a 3,500-watt strip at 230 volts should read about 230 x 230 / 3,500 = 15 ohms. OL means a broken coil. Test the high limit next to it for continuity at room temperature. It should read near 0 ohms. Also test from each strip terminal to the chassis, which should read OL.

The Run Capacitor

PTAC and window unit motors and compressors use run capacitors. A failed one shows up as a hum with no start, or a fan that will turn only if pushed. If your employer has trained and authorized you to replace capacitors, start only after the unit is unplugged or locked out and proven dead.

Warning: A capacitor can hold a dangerous charge after the power is off. Discharge it with a rated discharge tool or resistor, and confirm zero volts across every terminal, before you touch it. Never short it with a screwdriver.

Photograph the wiring, test the capacitor against its label on your meter's capacitance setting, and replace it with the same microfarad rating and the same or higher voltage rating. Move one wire at a time.

Window Units

Window units add a falling hazard. A unit that slips out of a window above a sidewalk can kill someone below.

  • Support the unit with the bracket its maker supplies or specifies, and fasten it to the window frame as the install guide shows. Building rules and some local laws require a bracket.
  • Install it with a slight tilt toward the outside, so condensate drains out and not into the room.
  • Seal the side panels, and lock the window sash down against the unit.
  • Before you remove a unit, have a helper hold it from inside. Never lean out the window to reach it.
  • The cleaning steps match a PTAC: filter, coils at low pressure, base pan and drain.

Repair or Replace

PTAC and window unit chassis are often cheaper to replace than to repair once the sealed system fails. Suspect the sealed system when the compressor runs, the coils are clean, airflow is good, and the unit still does not cool, or when the indoor coil frosts only partly. Oil stains on the tubing point to a leak. Any repair to the sealed system is for an EPA 608 Type I or Universal technician.

Many properties keep spare chassis of the same model. Swapping one in and sending the failed one out for repair or recycling gets the resident cool or warm the same day.

When a unit is scrapped, its refrigerant must be recovered before disposal. The last person in the disposal chain, often the scrap or recycling company, must confirm that it was. Send failed units through the recycler or hauler your property uses, with any paperwork they require. Never cut the refrigerant lines to "empty" a unit. That is illegal venting.

Common Mistakes

Mistake What it costs
Pressure-washing the coils Flattened fins and lost airflow
Putting wet filters back in Mold and a musty room
Bypassing the plug's protective device A cord fault that can start a fire
Leaving a sleeve tilted toward the room Water on the floor and rotted wall framing
Lifting a chassis alone A back injury or a dropped unit
Cutting lines on a unit headed for scrap Illegal refrigerant venting

Check Your Understanding

1. A PTAC is dead, and the reset button on its plug has popped out. You press it, and it trips again as soon as the unit starts. What do you do?

Leave it unplugged and tag it. The protective device is detecting a fault in the cord or the unit. Inspect the cord for damage, and replace the cord with the maker's part or swap the chassis. Never bypass the device.

2. Water drips onto the carpet under a PTAC. The filters and coils are clean. What do you check?

The sleeve's tilt, which should be slightly toward the outside, the base pan drain holes, and the seal between the chassis and sleeve.

3. A coworker wants to clean a PTAC coil with the pressure washer used on sidewalks. What do you tell them?

Use low pressure from a garden hose, from the clean side out. A pressure washer flattens the fins and blocks the airflow.

4. A window unit runs, its coils are clean, the fan moves air, but the air is not cold and the compressor is running. What is the likely problem, and what happens next?

A sealed-system problem, such as a refrigerant leak. Report it. Repair takes an EPA 608 Type I or Universal technician, and replacing the unit is often the better choice. If it is scrapped, the refrigerant must be recovered first.

Key Takeaways

  • Unplug the unit or lock out its breaker, and never bypass the cord's protective device.
  • Clean filters monthly and coils at least yearly, at low water pressure.
  • A PTAC sleeve is level side to side and tilts slightly toward the outside.
  • Discharge capacitors after the power is off and proven dead, and only if you are trained to replace them.
  • Sealed-system work needs EPA 608 Type I or Universal certification, and many new units use flammable refrigerants.
  • Scrapped units must have their refrigerant recovered before disposal.