Skills / Building Maintenance / Facilities Maintenance / No-Cool and No-Heat Calls for Maintenance Techs
Building Maintenance

No-Cool and No-Heat Calls for Maintenance Techs

20 min read Training Guide

Work a no-cool or no-heat call in order, from thermostat and power to filter, breakers, condensate switch and visual checks, and know where it becomes HVAC-tech work.

Table of contents

Many no-cool and no-heat calls never need an HVAC technician. A dead thermostat battery, a tripped float switch, a clogged filter or a breaker that tripped once will stop a system that has nothing wrong with it. Check in a fixed order, cheapest and safest first: thermostat, power, filter, breaker or disconnect, condensate safety switch, then visual checks. When the problem is in the refrigerant, the gas valve, the burners or the heat exchanger, the call belongs to a certified or licensed HVAC technician, and your job is to make it safe and hand it off with good notes.

What You Will Be Able to Do

  • Triage a no-cool or no-heat call and spot the ones that are emergencies
  • Check the thermostat, power, filter, breakers and disconnect in order
  • Find and clear a tripped condensate safety switch
  • Read what you see and hear at the indoor and outdoor units
  • Recognize HVAC-tech work and hand it off with useful notes

Before You Go

Ask the resident a few questions when the call comes in, or at the door:

  1. Is air coming out of the vents, and is it warm, cold or room temperature?
  2. What does the thermostat screen show?
  3. When did it start? Was there a storm or a power outage?
  4. Is there water on the floor, a burning smell, or a new noise?
  5. Has a carbon monoxide alarm sounded, or does anyone smell gas?

A gas smell or a CO alarm is not a repair call. Get people out, call from outside, and follow the emergency response. Your property's policy decides which calls are emergencies, and many cities set a minimum indoor temperature for rental housing in the heating season. No heat in freezing weather, or no cooling for a medically fragile resident in extreme heat, usually goes first.

Step 1: The Thermostat

Most calls that end in a few minutes end here.

  • Mode. Is it set to Cool or Heat, not Off or Fan?
  • Setpoint. For cooling, it must be several degrees below the room temperature. For heating, several degrees above.
  • Schedule. A program can change the setpoint during the day.
  • Fan setting. "On" runs the blower all the time, even between calls, which residents often read as warm air. "Auto" runs it only during a call.
  • Batteries. A blank or flickering screen on a battery thermostat often means dead batteries.
  • Short delay. Many thermostats wait several minutes, often about 5, before they restart the compressor. Give it time after you change a setting.

A screen that stays blank with fresh batteries may have lost its 24-volt power, often because a condensate safety switch tripped or a control fuse blew. Keep going.

Step 2: Power to the Indoor Unit

Find the indoor unit: a furnace or air handler in a closet, attic, basement or utility room.

  • Service switch. Most have a switch like a light switch on or near the unit, which people turn off by mistake.
  • Blower door. A door switch cuts power when the blower door is off. The door must be on and seated.
  • Status light. A steady or blinking light behind the door's small window means the board has power.

Step 3: The Filter

A clogged filter starves the system of air. In cooling, the indoor coil can freeze into a block of ice. In heating, the furnace overheats and shuts its burners off on a safety limit.

  1. Find the filter: at a return grille in a wall or ceiling, in a slot at the unit, or inside the air handler.
  2. Pull it and look at it against a light.
  3. Replace it with the same size, printed on its frame, with the airflow arrow pointing toward the unit.
  4. Write the date on the new filter's frame.

Step 4: Breakers and the Disconnect

A split system has one breaker for the indoor unit and one for the outdoor unit, which also has a disconnect box beside it.

  • Check both breakers. Push a tripped one fully off, then on, once, if your site allows it.
  • Check that the outdoor disconnect is on. A missing or reversed pull-out block stops the outdoor unit.
  • If a breaker trips again, stop. A second trip reports a fault, often in the compressor or a fan motor. Leave it off, tag it, and call it in.

Step 5: The Condensate Safety Switch

In cooling, the indoor coil pulls water out of the air, which drains through a pan and a pipe. If the drain clogs, a float switch shuts the system down before the water floods a ceiling. Building codes require a backup like this where an overflow would damage the building.

You will find the switch in one of these places:

  • In a secondary drain pan under an attic or closet air handler
  • On the primary drain line, near the unit, in a tee or a small clear box
  • Inside a condensate pump, which has its own float and often a safety switch wire

Signs it has tripped: water in the pan or drain line, and a system dead in cooling, sometimes with a blank thermostat.

Clearing It

  1. Turn off the system at the thermostat and the service switch.
  2. Find the end of the drain line, outside or at a floor drain. Seal a wet/dry vacuum hose over it with your hand or a rag and run it for a minute to pull the clog out.
  3. Flush the line from the unit end with water, or with a cleaner the equipment maker approves, through the cleanout or vent tee.
  4. Empty and dry the secondary pan, and clean any sludge.
  5. Make sure the float drops back down. Most reset on their own once the water is gone.
  6. Turn the system back on and watch water drain freely after several minutes of cooling.

Warning: Never bend a float switch, tape it down, or wire around it to get a system running. Without it, the next clog floods the ceiling or the unit below.

Step 6: Visual Checks

Look and listen. Do not reach into a running unit, and do not open electrical panels unless you are trained and authorized to.

When It Will Not Cool

What you see or hear What it usually means What to do
Indoor blower runs, outdoor unit silent Outdoor power, disconnect, contactor, or a control fault Recheck breaker and disconnect, then call it in
Outdoor fan does not spin, unit hums Failed run capacitor, or a stuck fan motor See the capacitor section below
Outdoor unit runs, air is not cold Dirty outdoor coil, low refrigerant, or a compressor problem Clean the coil area, then call it in
Ice on the indoor coil or the large copper line Low airflow, or low refrigerant Thaw it, fix airflow, call if it refreezes
Outdoor coil packed with cottonwood, lint or grass Heat cannot leave the unit Lock out and clean the coil gently
Burned smell, scorched wires visible Electrical fault Leave it off, tag it, call it in

A frozen coil. Set the thermostat to Off and the fan to On, so the blower thaws the ice. This can take hours, and the melt water can overwhelm the pan, so watch it. Do not chip the ice. Then fix the airflow: the filter, blocked returns or closed registers. If it freezes again with good airflow, the cause is likely low refrigerant, which is HVAC-tech work.

A temperature check. After about 15 minutes of cooling, measure the air at a return grille and a nearby supply register with a probe thermometer. Many technicians expect the supply to be roughly 14 to 22 degrees colder, but humidity changes that and grille readings are rough. Write both numbers down. A split near zero means air is moving but not being cooled.

When It Will Not Heat

Gas furnace.

  • Status light code. Match the blink pattern to the chart on the furnace door, and write it down.
  • Vent and intake pipes. Snow, ice or a nest over the ends of a high-efficiency furnace's plastic pipes outside will shut it down. Clear them gently.
  • Condensate trap and drain. A high-efficiency furnace makes water, and a clogged trap or drain will shut it off.
  • Gas supply. If you are trained and there is no gas smell, check that the furnace's gas shutoff handle is open. Do not relight anything if you smell gas.

Heat pump. Light frost on the outdoor coil is normal, and a defrost cycle clears it, sometimes with steam. A coil buried in solid ice is not normal, so check that snow or a roof drip is not burying it, and call it in. Check whether the thermostat is on emergency heat, which runs only the backup heat.

Electric baseboard and wall heaters. Check the breaker and the heater's thermostat. Many use a 240-volt thermostat on the wall, so do not open it or the heater cover unless you are trained and the circuit is locked out.

The Run Capacitor

A failed run capacitor is a common reason an outdoor unit hums without its fan or compressor starting. A bulged top or leaking oil is a strong sign. Replace one only if your employer has trained and authorized you. Otherwise, report what you saw.

If you are authorized:

  1. Turn off the outdoor disconnect and the breaker. Lock and tag them.
  2. Prove the unit dead at the contactor with your meter, testing the meter on a known live source before and after.

    Warning: A capacitor can hold a dangerous charge after the power is off. Only after the power is off and proven dead, discharge it with a rated discharge tool or resistor, then confirm zero volts across every terminal before you touch it. Never short it with a screwdriver.

  3. Photograph the wiring and label each wire by its terminal: C, HERM and FAN on a dual capacitor.

  4. Test it on your meter's capacitance setting and compare it with its label.

  5. Replace it with one of the same microfarad rating and the same or higher voltage rating.

  6. Move one wire at a time to the new capacitor, mount it, close the panel, and restore power. Watch both the fan and the compressor start.

If a new capacitor does not get the unit running, stop there and call it in.

Where It Becomes HVAC-Tech Work

Work Why
Anything involving refrigerant: gauges, adding, recovering, leak repair Requires EPA Section 608 certification, and topping off hides a leak
A coil that refreezes with good airflow Usually low refrigerant
Compressor and outdoor fan motor diagnosis or replacement Line-voltage live testing, and sealed-system risk
The furnace gas valve, burners, orifices and gas pressure Gas work for a qualified technician
Igniter or flame sensor work, unless your employer trained you on it Inside the burner compartment, next to the gas train
The heat exchanger, venting and combustion testing A cracked heat exchanger or a bad vent can poison people with CO
A tripped flame rollout switch Flames came out of the burner area, a serious fault. Never just reset it
Control boards, wiring changes and live voltage tests Need training and authorization for energized work

Make It Safe and Hand It Off

  1. If the unit is unsafe, turn it off, tag it out of service, and tell the resident why.
  2. Offer the interim help your property allows, such as fans or approved space heaters.
  3. Write up what you checked and found: settings, breakers, filter, float switch, temperatures, the status light code, and any sounds or smells.
  4. Tell the resident what happens next and when.

Common Mistakes

Mistake What it costs
Opening panels before checking the thermostat Time spent on a dead battery
Resetting a breaker again and again A damaged compressor, or a fire
Bypassing a float switch A flooded ceiling and the unit below
Chipping ice off a coil A punctured coil and a refrigerant leak
Changing a capacitor without proving the power dead A serious shock
Resetting a flame rollout switch and leaving A furnace that can start a fire or make CO

Check Your Understanding

1. The thermostat screen is blank, though the batteries are new. You find water in the pan under the attic air handler. What happened, and what do you do?

The condensate drain clogged and the float switch shut the system down. Turn it off, clear the drain line from its outdoor end with a wet/dry vacuum, flush it, dry the pan, and confirm the float resets and water drains during cooling.

2. The indoor blower runs and the air feels like room temperature. The large copper line at the indoor unit is covered in ice. What do you do?

Set the thermostat to Off with the fan On to thaw the coil, and watch the drain pan. Check the filter and the returns. If it freezes again with good airflow, call an HVAC technician, since low refrigerant is likely.

3. The outdoor unit hums, but its fan does not spin. The top of the capacitor is bulged. You have not been trained to replace capacitors. What do you do?

Turn off the disconnect, report what you saw, and call it in. The bulged capacitor is the likely cause, but the replacement is for someone trained and authorized, with the power locked out, proven dead and the capacitor discharged.

4. A furnace's status light blinks a code for a pressure switch, and outside you find the white intake pipe packed with snow. What do you do?

Clear the snow from the intake and exhaust pipes, then let the furnace try to restart. Record the code. If it does not restart, call it in.

Key Takeaways

  • Work in order: thermostat, power, filter, breaker or disconnect, condensate safety switch, then visual checks.
  • A gas smell or a CO alarm is an emergency response, not a repair call.
  • Reset a breaker once. A second trip means a fault.
  • Clear a tripped float switch by clearing the drain, never by bypassing it.
  • Thaw a frozen coil with the fan, fix airflow, and call if it refreezes.
  • Refrigerant, gas valves, burners, heat exchangers and live testing are HVAC-tech work. Hand off with good notes.