Smoke and Carbon Monoxide Alarm Maintenance

15 min read Training Guide

Test, place, replace and record smoke and carbon monoxide alarms in apartments, read chirps and date codes, and know where the building fire alarm system is off limits.

Table of contents

A working smoke alarm gives people the minutes they need to get out of a fire. A working carbon monoxide alarm warns them about a gas they cannot see or smell. In apartments, these alarms get disabled more often than almost anything else: pulled down because of cooking smoke, left chirping without a battery, or painted over during a turn. Checking them is a small job that you repeat in every apartment you touch, and it is one of the few tasks where your work may decide whether someone lives.

What You Will Be Able to Do

  • Tell a single-station alarm from a building fire alarm detector
  • Test smoke and carbon monoxide alarms and read their date codes
  • Explain where alarms belong and what causes false alarms
  • Replace an alarm with the right type, and replace it before it expires
  • Respond to a sounding carbon monoxide alarm, and keep records

Who Sets the Rules

Three layers apply, and the local one wins.

  1. NFPA 72, the National Fire Alarm and Signaling Code, published by the National Fire Protection Association, sets how alarms are installed, tested and replaced. States and cities adopt it, often through their building and fire codes.
  2. State and local law decides which apartments need which alarms, what kind of power they use, whether 10-year sealed batteries are required, who must test them, and what records are kept.
  3. The manufacturer's instructions decide placement details, testing steps and the alarm's service life.

Your supervisor should know which code edition and state rules apply to your property. If the rules and the manufacturer disagree, ask before you act.

Know What You Are Looking At

Device What it is Who works on it
Single-station smoke alarm Self-contained detector and horn, battery or hardwired Maintenance, if trained
Interconnected smoke alarms Hardwired alarms wired together in one apartment so all sound at once Maintenance, if trained, with matching replacements
Carbon monoxide (CO) alarm Detects CO, plug-in, battery or hardwired Maintenance, if trained
Combination smoke and CO alarm Both sensors in one device, with different alarm sounds Maintenance, if trained
System smoke detector Connected to the building's fire alarm panel, usually with no test button Licensed fire alarm contractor only

Warning: Do not test, remove, cover or replace a detector connected to the building fire alarm system. Testing it can send the fire department, and removing it can leave the building unprotected. Report problems with it to your supervisor and the fire alarm company.

Where Alarms Belong

NFPA's guidance for homes is a smoke alarm inside every bedroom, outside each separate sleeping area, and on every level. CO alarms go in a central location outside each sleeping area and on every level, and anywhere else your code requires. Mount them on the ceiling or high on a wall as the manufacturer directs.

Placement also prevents false alarms, which are the main reason residents disable alarms.

  • Keep smoke alarms at least 10 feet from cooking appliances when the layout allows. Follow the manufacturer and your code for small kitchens, where photoelectric alarms or models with a silence button may be required.
  • Keep alarms away from bathroom doors, where shower steam drifts out.
  • Keep them out of the direct airflow of supply vents and away from ceiling fans, which can blow smoke away from them.
  • Do not paint them, cover them, or put stickers on them.

If an alarm keeps going off from cooking, do not move it on your own. Report it, so your supervisor can choose a compliant fix, such as a different alarm type or a new location the code allows.

Testing Alarms

Test alarms at every turn, on every scheduled check, and whenever you are in an apartment for a related call. NFPA recommends that residents test their alarms monthly.

  1. Tell the resident before you test, since the sound is loud. In an occupied apartment, warn neighbors if alarms are interconnected through walls.
  2. Look first. Check that the alarm is present, mounted, not painted, not covered by a bag or tape, and not hanging by its wires.
  3. Read the date. Find the date of manufacture on the back or side. Remove the alarm from its base if you need to, then reinstall it.
  4. Press and hold the test button until the alarm sounds. Use the end of a broom handle or a ladder, never a chair.
  5. Check interconnection. When you test one interconnected alarm, every alarm in the apartment should sound.
  6. Test CO alarms with their test button the same way. A combination unit may have one button that tests both.
  7. Look at the indicator lights for power and trouble, as the manufacturer describes them.
  8. Record the results.

The test button checks the horn and the electronics. It does not prove the sensor will detect smoke, so an alarm past its replacement date gets replaced even if the test button works.

Chirps and Signals

A short chirp every so often is the alarm asking for attention. What it means depends on the model, so check the label or manual.

Signal Common meaning What to do
A single chirp about once a minute Low battery Replace the battery, or the alarm if it has a sealed battery
A different chirp pattern, often several chirps End of life Replace the whole alarm
Chirping after a new battery Battery not seated, wrong battery, or alarm needs reset Reseat, check the battery type, follow the reset steps
Hardwired alarm chirping Backup battery low or missing Replace the backup battery
Full alarm with no smoke Cooking, steam, dust, insects, or a failing alarm Check for a cause, clean as directed, replace if it repeats

Never leave an alarm with the battery pulled to stop a chirp. Replace the battery or the alarm before you leave.

Replacing Alarms

When

NFPA 72 says smoke alarms must be replaced no later than 10 years after the date of manufacture, and sooner if they fail a test. The date is printed on the alarm. An alarm made in March 2016 is due by March 2026, even if it was installed in 2019.

CO alarms have a shorter or different life set by the manufacturer. Many newer CO alarms sound an end-of-life signal when their sensor is spent. Replace a CO alarm when it signals end of life or reaches the date the manufacturer gives, whichever comes first.

Worked example. During a turn, you find three alarms. The hallway smoke alarm is dated 2014-07. The bedroom smoke alarm is dated 2021-02. The CO alarm is dated 2019-05, and its label says to replace it 7 years after manufacture. It is now November 2026. The hallway alarm is past its 10 years, so replace it. The bedroom alarm is good until February 2031. The CO alarm reached its 7 years in May 2026, so replace it too.

With What

Replace like with like, or with what your code and property standard require.

  • Battery alarm: a model of the same type, or a 10-year sealed battery model if your state requires it.
  • Hardwired alarm: a hardwired model with battery backup, using a compatible connector. Interconnected alarms usually must be the same brand or a listed compatible model, or the alarms will not talk to each other.
  • Combination alarm: another combination alarm, or separate smoke and CO alarms, so nothing is lost.

Changing a hardwired alarm means working on a 120-volt circuit. Turn off the breaker, prove the wires dead with a tester, and use the manufacturer's connector. If the wiring is damaged, missing a box, or needs to be changed, stop and call an electrician.

Write the installation date on the new alarm if your property does that, and make sure the date of manufacture can still be read.

Residents Who Are Deaf or Hard of Hearing

Some residents need alarms with strobe lights or bed shakers. A request for one is usually a request for a reasonable accommodation or modification, so pass it to the office the same day without asking about the person's hearing.

When a CO Alarm Sounds

Carbon monoxide comes from fuel-burning equipment such as gas furnaces, water heaters, ranges, fireplaces, and cars or generators running in or near the building. Early symptoms include headache, dizziness, nausea and confusion.

  1. Get everyone out to fresh air right away.
  2. Call 911 from outside. Then call your supervisor and the gas utility as your policy says.
  3. Do not go back in, and do not let anyone else in, until the fire department or utility says it is safe.
  4. Do not just reset the alarm and leave. A CO alarm that went off for a reason will go off again.
  5. Keep the fuel-burning equipment off until a qualified technician has inspected it.

Records

A clear record shows the property met its duties and tells the next tech what to expect. For each alarm, record:

  • Apartment and location, such as "hall outside bedrooms"
  • Type: smoke, CO, or combination, and battery, sealed battery, or hardwired
  • Date of manufacture
  • Date tested and the result
  • Battery or alarm replaced, and the date
  • Your initials

Many properties also have new residents sign at move-in that the alarms were tested and working, and some states require a test at the start of each tenancy. Keep records as long as your policy or state law says.

Common Mistakes

Mistake What it costs
Pulling the battery to stop a chirp An apartment with no working alarm
Leaving a painting cover on an alarm An alarm that cannot sense smoke
Trusting the test button on an old alarm A sensor that may no longer detect smoke
Mixing brands on interconnected alarms Alarms that do not sound together
Testing a system detector A false call to the fire department
Resetting a CO alarm without finding the cause A resident poisoned later

Check Your Understanding

1. You are testing alarms in a turn. The bedroom alarm sounds when you press the button. The date on the back is 11 years ago. Does it stay?

No. Smoke alarms must be replaced no later than 10 years from the date of manufacture. The test button only checks the horn and electronics.

2. A resident complains that the smoke alarm goes off every time she cooks and asks you to take it down. What do you do?

Leave it up and working. Check that it is not too close to the range, and report it so your supervisor can choose a fix the code allows, such as a photoelectric model or a new location.

3. A ceiling detector in a hallway outside the apartments has no test button and is wired to a panel in the electrical room. A resident says it is blinking. What do you do?

Leave it alone. It is a system detector on the building fire alarm. Report it to your supervisor so the fire alarm company can check it.

4. A combination alarm in an occupied apartment is sounding the CO pattern. The resident has a headache. What do you do?

Get everyone out to fresh air and call 911 from outside. Call your supervisor and the gas utility as your policy says, and keep everyone out until responders say it is safe. Do not reset the alarm and leave.

Key Takeaways

  • NFPA 72, state law and the manufacturer set the rules, and the local rule wins.
  • Keep your hands off detectors connected to the building fire alarm system.
  • Put alarms inside bedrooms, outside sleeping areas and on every level, away from cooking, steam and moving air.
  • Test with the button, read the date, and replace smoke alarms by 10 years from manufacture.
  • Replace CO alarms at end of life or by the manufacturer's date, and treat a sounding CO alarm as a 911 call.
  • Record every test and replacement.